ORDINANCE NO. BL2002-1142
AN ORDINANCE AMENDING CHAPTERS 2, 10, 15 AND 16 OF THE METROPOLITAN CODE OF LAWS BY ADOPTING THE LATEST EDITIONS OF THE NFPA FIRE CODES, THE STANDARD CODES (BUILDING, GAS, MECHANICAL, PLUMBING) AND THE INTERNATIONAL ENERGY CONSERVATION CODE AND AMENDMENTS THERETO AND CORRECTING OUTDATED PROCEEDURES AND CLARIFYING AN ELECTRICAL AMENDMENT.
Section 1. Section 2.28.130 of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.130 and substituting the following:
“2.28.130
Laws and ordinances--Enforcement authority.
It shall be the duty of the fire marshal to enforce within Davidson County (except
for the city of Goodlettsville) all laws and ordinances relating to:
A. The prevention of fires;
B. The storage, sale and use of combustibles and explosives;
C. The installation and maintenance of automatic or other fire alarm systems
and fire-extinguishing equipment;
D. The construction, maintenance and regulation of fire escapes;
E. The means and adequacy of exits, in case of fire, from factories, asylums,
hospitals, churches, schools, halls, theaters, amphitheaters, and all other
places in which numbers of persons live, work or congregate from time to time
for any purpose.”
Section 2. Section 2.28.140 of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.140 and substituting the following:
“2.28.140
Investigation of fires—Record keeping.
It shall be the duty of the fire marshal to attend fires occurring within Davidson
County(except for the city of Goodlettsville), and to make investigation and
ascertain the cause, origin and circumstances of all such fires. He shall keep
records, in which he shall record the date of each fire, the place, the character
of the building or structure, the name of the owner, lessee or occupant, the
amount of loss caused by the fire, the amount of insurance carried on the building,
the amount of insurance carried on stock or contents, the cause or origin of
the fire, and any other fact ascertained in the course of his investigation,
together with the names and addresses of any witnesses thereto.”
Section 3. Section 2.28.160 of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.160 and substituting the following:
“2.28.160
Police powers of fire marshal.
The fire marshal and his designees shall have police powers within Davidson
County.”
Section 4. Section 2.28.170A of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.170A and substituting the following:
“2.28.170
Orders to remedy dangerous conditions--Appeals.
A. Whenever the fire marshal shall find any building or other structure within
the county which, for want of repair or by reason of age or dilapidated condition,
or for any cause, is especially liable to fire, and which is so situated as
to endanger other buildings, structures or property, or whenever he shall find
in any building or structure within the urban services district an improper
or dangerous arrangement or condition of stoves, ranges, furnaces or other heating
appliances of any kind whatsoever, including chimney, flues and pipes with which
the same may be connected, or a dangerous condition or arrangement of lighting
devices or system, or a dangerous or unlawful storage of explosives, petroleum,
gasoline, kerosene, dangerous chemicals, vegetable products, fireworks, ashes,
combustibles, inflammables, or refuse materials, or other conditions which,
in his opinion, may constitute a dangerous fire hazard, or be liable to cause
or promote fire or to create conditions dangerous to the emergency responders
or to occupants of the building or to adjoining property, he shall serve an
order in writing upon the owner, lessee, occupant or agent of the building for
the dangerous condition or arrangement, specified and described in such written
order, to be removed or remedied, within a time, not less than five days, to
be designated in the order, and such order shall be within the designated time
complied with by the owner, lessee and occupant or agent of such building; provided,
that if the owner, lessee, occupant or agent deems himself aggrieved by such
order, he may, before the next meeting of the Board of Fire and Building Code
Appeals, from the service of such order, appeal to said board, by written petition
addressed to the board who shall hear such appeal as soon as it can be conveniently
heard, and who may make investigation and hear testimony of any witnesses, and
issue subpoena for any witnesses, and who may, upon such hearing, either affirm,
modify or revoke the order of the fire marshal. If the order of the fire marshal
is affirmed or modified, such order so affirmed or modified shall forthwith
be complied with by the owner, lessee, occupant or agent.”
Section 5. Section 2.28.180B of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.180B in its entirety.
Section 6. Sections 2.28.190 and 2.28.200 of the Metropolitan Code of Laws is hereby amended by deleting Sections 2.28.190 and 2.28.200 in their entirety.
Section 7. Section 2.28.210 of the Metropolitan Code of Laws is hereby amended by deleting Section 2.28.210 and substituting the following:
“2.28.210
Assistant fire marshal--Right of entry for inspection.
The assistant fire marshal, in aiding and assisting the fire marshal in the
discharge of the duties of fire marshal under the ordinances of the metropolitan
government and the law, shall have the right at all reasonable hours, for the
purposes of examination, to enter into and upon all buildings and premises within
in Davidson County.”
Section 8. Section 10.64.010 of the Metropolitan Code of Laws is hereby amended by deleting Section 10.64.010 and substituting the following:
“10.64.010
Fire prevention code adopted
The metropolitan government adopts the 2000 Fire Prevention Code of the National
Fire Protection Association (Fire Prevention Code), which references the 2000
edition of the printed volumes of the National Fire Code, as amended in this
chapter, to be applicable throughout the metropolitan government. A copy of
such fire prevention code is attached to the ordinance codified in this section
and made a part hereof, the same as if copied verbatim herein.”
Section 9. Chapter 10.64. of the Metropolitan Code of Laws is hereby amended by adding the following new Section 10.64.012:
“10.64.012
Amendments to the 2000 NFPA Fire Prevention Code
The following amendments, deletions, or additions to the 2000 FIRE Prevention
are adopted by reference, as fully as though copied into such Fire Code, and
thereby made a part of the Metropolitan Fire Prevention Code.”
A. Section 1-4 of the 2000 edition of the NFPA 1, Fire Prevention Code, which is part of the National Fire Codes, is hereby amended by adding the following new Section 1.4.17:
1.4.17 The provisions of this code do not apply to one and two family dwellings in the normal use or maintenance thereof.
Exception No. 1: This code shall apply whenever the activity or use of such dwelling creates a fire hazard to life or property.
Exception No. 2: Where provisions of annexed codes specifically apply to one or two-family dwelling.
B. Section 1-7 of the 2000 Fire Prevention Code is hereby amended by deleting Section 1-7 and substituting the following:
The Board of Appeals created and empowered to act on all appeals under this Metropolitan Fire Prevention Code shall be the Metropolitan Board of Fire and Building Code Appeals (Board) as established and provided for in the Metropolitan Code of Laws, Chapter 2.80 and Section 16.08.010. The Board shall hear all appeals for variances in or interpretations of this Metropolitan Fire Prevention Code by the Fire Marshal of the Metropolitan Government. When acting under this Metropolitan Fire Prevention Code, the Board shall transmit its decisions to the Fire Marshal.”
C. Section 1-16.16 (13) of the 2000 Fire Prevention Code is hereby amended by deleting Section 1-16.16(13) and substituting the following:
(13) Explosives. Manufacture, sell, dispose, purchase, storage, use, possess, or transport of explosives within the jurisdiction. A separate permit, valid for the duration of the project but not to exceed one year, shall be required to conduct blasting operations.
D. Section 1-16.16 of the 2000 Fire Prevention Code is hereby amended by adding a item (37) to Section 1-16.16 as follows:
(37) Large indoor
assembly exceeding 4,000 persons.
Exception: Facilities whose only use is for worship.
E. Section 1-16.17of the 2000 Fire Prevention Code is hereby amended by deleting Section 1-16.17 and substituting the following:
Permit fees shall be established by the authority having jurisdiction.
F. Section 3-1 of the 2000 edition of the NFPA 1, Fire Prevention Code, which is part of the National Fire Codes, is hereby amended by adding the following new Section 3-1.3.1:
3-1.3.1 No person shall knowingly maintain a fire hazard.
G. Section 7-3.2.21.2.2 The 2000 Edition of NFPA 1, which is a part of the National Fire Code, is hereby amended by deleting subsection 7-3.2.21.2.2 and substituting the following:
7-3.2.21.2.2 The entire building shall be required to be protected by an approved, automatic sprinkler system by January 3, 2007.
H. Section 7-7.3 of the 2000 Edition of NFPA 1, which is a part of the National Fire Code, is hereby amended by adding the following new subsection 7-7.3.2.3.
7-7.3.2.3- A State of Tennessee licensed Fire Alarm contractor shall complete an inspection of any fire alarm system annually. A copy of this report stating the findings ( compliance and violations ) shall be provided to the authority having jurisdiction within 10 working days of the inspection. Repairs as a result of this inspection that will take more than 24 hours to complete shall be reported to the authority having jurisdiction immediately.
I. Section 16-10.1 of the 2000 Edition of NFPA 1, The Fire Prevention Code which is a part of the National Fire Code is hereby amended by deleting subsection 16-10.1 and substituting the following:
16-10.1 Application. Where permitted, the storage and wholesale, of consumer fireworks (DOT Classified) shall be in accordance with this section to ensure public safety. All storage of display fireworks shall comply with NFPA 1124, Code for the Manufacture, transportation, and storage of Fireworks and Pyrotechnic Articles.
J. Section 28-2.8.9 of the 2000 edition of NFPA 1, the Fire Prevention Code which is a part of the National Fire Code is hereby amended by deleting subsection 28-2.8.9 and substituting the following:
28-2.8.9 Signs.
Warning signs shall be conspicuously posted in the dispensing area incorporating
the following or the equivalent wording:
(1) WARNING – It is unlawful and dangerous to dispense gasoline into unapproved
containers.
(2) No Smoking
(3) Stop Motor
The words WARNING, No Smoking and Stop Motor shall be at least four inches in
height with a stroke width of one inch. They shall be in a contrasting color
that is acceptable to the Authority Having Jurisdiction.
Section 10. Chapter 10.64.015 of the Metropolitan Code of Laws is hereby amended by deleting Section 10.64.015 and substituting the following:
10.64.015 Amendments
to the 2000 NFPA 101 Life Safety Code
The following amendments, deletions, or additions to the 2000 NFPA Life Safety
Code are adopted by reference, as fully as though copied into such Fire Code,
and thereby made a part of the Metropolitan Fire Prevention Code.
A. Section 3-3 of the 2000 Edition of the NFPA 101, Life Safety Code, which is apart of the National Fire Code, is hereby amended by adding the following definition at the end of Section 3-3:
3-3.214 Bed and breakfast homestay. A private home, inn or other unique residential facility located in a structure of historical significance as defined in Tennessee Code Annotated Section 68-14-503(3), offering bed and breakfast accommodations and one (1) daily meal and having less than four (4) guest rooms furnished for pay, with guests staying not more than fourteen (14) days, and where the innkeeper resides on the premises or property, or immediately adjacent to it. Guest rooms shall be established and maintained distinct and separate from the innkeeper's quarters.
B. Section 3-3.196 of the 2000 Edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting subsection 3-3.196 and substituting the following:
3.3.196 STREET FLOOR.- A story or floor level accessible from the street or from the outside of a building at ground level, with the floor level at the main entrance located not more than three risers above or below ground level and arranged and utilized to qualify as the main floor or level of exit discharge.
C. Section 7.1.3.2.1(b) Exception No. 3 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting Exception No. 3.
D. Section 8.2.1(1) of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting subsection 8.2.1(1) and substituting the following:
8.2.1(1) Separate
buildings if a 4-hour or greater vertically-aligned fire wall in accordance
with NFPA 221, Standard for Fire Walls and Fire Barrier Walls, exists between
the portions of the building
Exception: The requirement of 8.2.1(1) shall not apply to previously approved
separations between buildings.
E. Section 9.7.2 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by adding the following new subsection 9.7.2.1.1:
9.7.2.1.1- Fire Pumps used in fire protection shall have the following signals transmitted to an approved Central Station Alarm Monitoring Service or an approved Proprietary Service:
Electric Fire Pumps
Diesel Fire Pumps
1. Fire Pump Run 1. Fire Pump Run
2. Phase Reversal 2. Low Batteries
3. Power Failure 3. Failure to Start
4. Main Water Flow 4. Main Water Flow
F. Section 11.8 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by adding the following new subsection 11.8.6:
11.8.6 Operating Features- A written Emergency Evacuation Plan approved by the Authority Having Jurisdiction shall be provided in the Fire Control Room. In existing buildings that do not have a fire control room the plan shall be accessible at the buildings Fire Alarm annunciator panel
G. Section 15.3.1 Exceptions (a), (b) and (c) of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting all Exceptions including (a), (b) and (c) in their entirety.
H. Section 16.2.2.1 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting subsection 16.2.2.1 and substituting the following:
16.2.2.1- Components of means of egress shall be limited to the types described in 16.2.2.2 through 16.2.2.7.
I. Section 17.2.2.1 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting subsection 17.2.2.1 and substituting the following:
17.2.2.1- Components of means of egress shall be limited to the types described in 17.2.2.2 through 17.2.2.7.
J. Section 28.2.2.1.2 of the 2000 edition of the NFPA 101 Life Safety Code, which is a part of the National Fire Code, is hereby amended by deleting subsection in its entirety.
K. Section 29.2.2.1.2 of the 2000 edition of the NFPA 101 Life Safety Code, which is part of the National Fire Code is hereby amended by deleting the subsection in it’s entirety.
Section 11. Chapter 10.64 of the Metropolitan Code of Laws is hereby amended by adding a new Section 10.64.017 as follows:
10.64.017 Amendments to Miscellaneous NFPA Codes & Standards (Sprinkler, Stationary pumps & Fire Walls etc.)
The following amendments, deletions, or additions to the NFPA Codes are adopted by reference, as fully as though copied into such Fire Code, and thereby made a part of the Metropolitan Fire Prevention Code.
A. Section 7-2.3.2.4 of the 1999 edition of the NFPA 13 Standard for the Installations of Sprinkler Systems which is a part of the National Fire Code, is hereby amended by deleting subsection 7-2.3.2.4 in its entirety.
B. Section 7-2.3.3 of the 1999 edition of the NFPA 13 Standard for the Installations of Sprinkler Systems which is a part of the National Fire Code adopted by reference herein, is amended by deleting subsection 7-2.3.3 in its entirety.
C. Section 5-13.14 of the 1999 edition of the NFPA 13 Standard for the Installations of Sprinkler Systems which is a part of the National Fire Code adopted by reference herein, is amended by deleting section 5-13.14 in its entirety.
D. Section 10-1
of the 1999 edition of the NFPA 13 Standard for the Installations of Sprinkler
Systems which is a part of the National Fire Code, is hereby amended by deleting
Section 10-1 and substituting the following .
10-1 Approval of Sprinkler Systems and Private Fire Service Mains.
The installing contractor shall be a licensed State of Tennessee Sprinkler Contractor
and shall do the following:
(1). Notify the authority having jurisdiction and owner’s representative
of the time and date testing will be performed
(2). Perform all required acceptance tests (see Section 10-2)
(3). Complete and sign the appropriate contractor’s material and test
certificate(s) [see Figures 10-1(a) and 10-1(b)]
(4). Shall be responsible for the installation of Fire Protection Sprinkler
Systems from the point of underground connection to the approved water supply,
beginning were the line becomes solely a fire protection line.
E. Section 2-7.1.1 Exception No. 2 of the 1999 edition of NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection which is a part of the National Fire Code, is hereby amended by deleting section 2-7.1.1 Exception No. 2 in its entirety.
F. Section 6-1 of the 2000 edition of NFPA 221 Standard for Fire Walls and Fire Barriers which is a part of the National Fire Code is hereby amended by deleting Section 6-1 and substituting the following:
6.1* Pipes, Raceways,
and Cables.
Pipes, raceways, and cable trays (regardless of size) penetrating fire walls
having a required 3-hour fire resistance rating shall be positioned to pass
through the wall no more than 3 ft (1.0 m) above the finished floor level. A
steel sleeve of a size to allow an approximate 1-in. (25-mm) clearance between
the sleeve and the pipe or raceway shall be provided for each pipe or raceway.
The space between the sleeve and penetrating item (annular space) shall be filled
as required in Section 4.2. Joint reinforcement shall be provided in the horizontal
mortar joints immediately above and below sleeves in concrete masonry walls,
and all hollow spaces of concrete masonry walls immediately adjacent to the
sleeve shall be filled with concrete, mortar, or grout.”
BUILDING CODE SECTION
Section 12. Section 16.08.010A of the Metropolitan Code of Laws is hereby amended by deleting Section 16.08.010A and substituting the following:
“A. 2000 Edition of the Standard Building Code, Sections 201 through 1611.3, Sections 1613 through 3408.8.5, Chapter 35 inclusive and Appendices C, D, H;
Section 13. Section 16.08.010D of the Metropolitan Code of Laws is hereby amended by deleting Section 16.08.010D and substituting the following:
"D. 2000 Edition of the International Energy Conservation Code, Sections 1.01.1 through Chapter 9 inclusive, and Appendix . This code edition shall apply to 1 & 2 family Dwellings, and commercial buildings."
Section 14. Section 16.08.012 of the Metropolitan Code of Laws is hereby amended by deleting Section 16.08.012 and substituting the following:
16.08.012 Amendments
to the Standard Building Code.
The following amendments, deletions, or additions to the 2000 Edition of the
Standard Building Code are adopted by reference, as fully as though copied into
such Building Code, and thereby made a part of the Building Code.
A. Section 201 of the 2000 Edition of the Standard Building Code is hereby amended by adding the following new Section 201.5 to Section 201:
201.5 Interchangeability with the Standard Codes. The International Building Code shall be construed to mean the Standard Building Code. The International Property Maintenance Code shall be construed to mean the Property Standards Code of the Metropolitan Government. The International Mechanical Code shall be construed to mean the Standard Mechanical Code. The International Fuel Gas Code shall be construed to mean the Standard Gas Code. The International Plumbing Code shall be construed to mean the Standard Plumbing Code. The International Private Sewage Disposal Code shall be construed to mean the Subsurface Sewage Disposal Systems Code of the Metropolitan Government The ICC Electrical Code shall be construed to mean the National Electrical Code.
B. Section 202 of the 2000 Edition of the Standard Building Code is hereby amended by adding the following new definitions:
BED AND BREAKFAST
HOMESTAY -- means a private home, inn, or other unique residential facility
located in a structure of historical significance as defined in Tennessee Code
Annotated Section 68-14-503(3) offering bed and breakfast accommodations and
one (1) daily meal and having less than four (4) guest rooms furnished for pay,
with guests staying not more than fourteen (14) days, and where the innkeeper
resides on the premises or property, or immediately adjacent to it. Guest rooms
shall be established and maintained distinct and separate from the innkeeper's
quarters.
BREEZEWAY – A covered connector between two buildings or structures, open
at each end but less than 50 percent open, located at, above, or below grade
level, that may be used as a means of egress from a building or structure.
BOARD -- shall mean the Metropolitan Board of Fire and Building Code Appeals.
CODE OFFICIAL - shall mean the Director of the Metropolitan Department of Codes
Administration, his deputy or duly authorized representative.
DIRECTOR -- shall mean the Director of the Metropolitan Department of Codes
Administration, his deputy or duly authorized representative.
FAMILY -- is an individual, two or more persons related by blood, marriage or
law, or a group of not more than any five unrelated persons living together
in a dwelling unit.
FARM ACCESSORY BUILDING -- shall be defined as barns, animal and poultry houses,
silos, storage and feed sheds, animal shelters and similar farm structures provided
that no such building or structure is designed for or intended to be used as
a place of human habitation.
EXIT DISCHARGE, LEVEL OF. -- (1) The lowest story from which not less than 50
percent of the required number of exits and not less than 50 percent of the
required egress capacity from such a story discharge directly outside at grade;
(2) the story with the smallest elevation change needed to reach grade where
no story has 50 percent or more of the required number of exits and 50 percent
or more of the required egress capacity from such a story discharge directly
outside at grade.
NORMAL MAINTENANCE REPAIRS -- shall be defined as repairs to an existing building
or structure, including but not limited to exterior and interior painting, papering,
glazing of windows and doors, floor finishing, minor repairs to chimneys, stairs,
porches, underpinning, and repairs to an existing roof not to exceed 33 percent
of the roof area.
PHYSICAL VALUE -- shall mean the actual cost of replacement of a building or
structure with materials of a like kind erected of a like manner to that of
the original construction or the physical value shall be the fair market value
or the appraised value of the building or structure, exclusive of land values,
as may be recorded in the Tax Digest of the Metropolitan Government whichever
shall be greater.
PREPARED ROOF COVERINGS -- shall be defined as those roof coverings consisting
of manufactured shingles or manufactured sheet coverings composed of asbestos
cement, asphalt asbestos, asbestos organic felt, asphalt glass fiber prepared
shingles or sheet roof coverings approved by Underwriters' Laboratories, Inc.
SELF-SERVICE STORAGE FACILITY AND/OR MINI-WAREHOUSE -- means any real property
designed and used for the purpose of renting or leasing individual storage space
to occupants who are to have access to such space for the purpose of storing
and removing personal property; provided, however, that the term "self-service
storage facility" or "mini-warehouse" shall not include any real
property used for residential purposes.
STREET FLOOR. -- A story or floor level accessible from the street or from outside
a building at ground level, with the floor level at the main entrance located
not more than three risers above or below ground level and arranged and utilized
to qualify as the main floor.
TEMPORARY -- shall mean not more than 90 calendar days.
C. Section 202 of the 2000 Edition of the Standard Code is hereby amended by deleting the definition of “Building Official” and substituting the following definition to Section 202:
BUILDING OFFICIAL -- shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
D. Section 310.1, subsection R-3 and R-4 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 310.1 subsection R-3 & R-4 and substituting the following:
R3: Residential
occupancies include the following:
One and two family dwellings where occupants are primarily permanent in nature
and not classified as R1, R2, R4 or I.
Rooming houses (transient) providing accommodations for 5 or fewer persons.
Bed and breakfast home stays R3.
Adult and child care facilities which accommodate five or less adults or children
of any age for any time period.
R-4 Residential occupancies shall include buildings arranged for occupancy as Residential Care/Assisted Living Facilities including more than five but not more than 16 occupants, excluding staff.
E. Section 501.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 501.2 and substituting the following:
501.2. Premises
Identification. All buildings and structures within Metropolitan Nashville and
Davidson County shall have approved address numbers posted in accordance with
following:
1. Residences are to have their numbers at least three (3) inches in size, on
a contrasting background, and in a position to be plainly visible and legible
from the street or road fronting the property. The numbers may be attached to
the residence or the mailbox, if the mailbox is next to the street.
2. Numbers posted on the outside of nonresidential buildings must be six inches,
or larger, on a contrasting background, and in a position to be plainly visible
and legible from the street or road fronting the premises. Numbers posted on
interior doors or spaces (such as a lease space in a mall) must be at least
three inches in size.
3. Multifamily buildings shall have their numbers displayed to be plainly visible
and legible, on a contrasting background, and a minimum size of six inches in
height. Identifying numbers, at least three inches in height shall also be posted
on or at the doors of individual dwelling units.
F. Section 502 of the 2000 Edition of the Standard Building Code is hereby amended by deleting the definition for “basement” and substituting the following:
BASEMENT. That
portion of a building that is partly or completely below grade plane (See "Story
above grade plane"). A basement shall be considered as a story above grade
plane where the finished surface of the floor above the basement is:
1. More than 6 feet (1829 mm) above average grade plane;
2. More than 6 feet (1829 mm) above the finished ground level for more than
50 percent of the perimeter of the basement, or
3. More than 12 feet (3658 mm) above the finished ground level at any point.
G. Section 503.3 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 503.3 in its entirety.
H. Section 505.1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 505.1 and substituting the following:
505.1 General. A mezzanine or mezzanines in compliance with this section shall be considered a portion of the floor below. Such mezzanines shall not contribute to the building area as regulated by Section 503.1. Such mezzanines shall not contribute to the number of stories as regulated by section 503.1. The area of the mezzanine shall be included in determining the fire area defined in Section 702. The clear height above and below the mezzanine floor construction shall not be less than 7.5 feet (2286 mm). The construction of a mezzanine shall be consistent with the type of materials and fire resistance ratings required for the building in which it is constructed.
I. Section 504.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 504.2 and substituting the following:
504.2 Automatic
sprinkler increase. For buildings protected throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.1, the value specified
in Table 503 for maximum height is increased by 20 feet (6096 mm) and the maximum
number of stories is increased by one story. These increases are permitted in
addition to the area increase.
EXCEPTIONS:
1. Group I-2 of Type IIB, III, IV or V construction.
2. Group H-1, H-2, H-3 or H-5.
J. Section 505.4 Exception 2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 505.4 Exception 2 and substituting the following:
2. In sprinklered buildings, a mezzanine having two or more means of egress need not open into the room in which it is located if the areas are of the same occupancies and if at least one of the means of egress provides direct access to an exit at the mezzanine level. The mezzanine can not exceed one third of the open area of the room or space in which is located.
K. Sections 507.1, 507.2 and 507.3 of the 2000 Edition of the Standard Building Code are hereby amended by deleting Sections 507.1, 507.2 and 507.3 and substituting the following:
507.1 Unsprinklered, one-story. The area of a one-story, Group F-2 or S-2 building of Type IB, II, III or IV construction shall not be limited when the building is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width.
507.2 Sprinklered, one-story. The area of a one-story, Group A-4, B, F, M or S building of Type IB, II, III or IV construction shall not be limited when the building is provided with an automatic sprinkler system throughout in accordance with Section 903.3.1.1, and is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width.
EXCEPTIONS:
1. Buildings and structures of Types I and II construction for rack storage facilities, which do not have access by the public shall not be limited in height provided that such buildings conform to the requirements of Section 507.1 and NFPA 231C.
2. The automatic sprinkler system shall not be required in areas occupied for indoor participant sports, such as tennis, skating, swimming and equestrian activities, in occupancies in Group A-4, provided that:
2.1. Exit doors directly to the outside are provided for occupants of the participant sports areas, and
2.2. The building is equipped with a fire alarm system with manual fire alarm boxes installed in accordance with Section 907.
507.3 Two-story. The area of a two-story, Group B, F, M or S building of Type IB, II, III or IV construction shall not be limited when the building is provided with an automatic sprinkler system in accordance with Section 903.3.1.1 throughout, and is surrounded and adjoined by public ways or yards not less than 60 feet (18 288 mm) in width.
L. Section 508.6 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 508.6 and substituting the following:
508.6 Group R-2 buildings of Type IIIA construction. The height limitation for buildings of Type IIIA construction in Group R-2 shall be increased to six stories and 75 feet (22 860 mm) where the first floor construction above the basement has a fire-resistance rating of not less than 3 hours and the floor area is subdivided by 2-hour fire-resistance-rated walls into areas of not more than 3,000 square feet (279 m2) when the building is provided with an automatic sprinkler system throughout in accordance with Section 903.3.1.1.
M. Section 508.7 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Sections 508.7 and substituting the following:
508.7 Group R-2 buildings of Type IIA construction. The height limitation for buildings of Type IIA construction in Group R-2 shall be increased to nine stories and 100 feet (30 480 mm) where the building is separated by not less than 50 feet (15 240 mm) from any other building on the lot and from property lines, the building is provided with an automatic sprinkler system throughout in accordance with Section 903.3.1.1, the exits are segregated in an area enclosed by a 2-hour fire-resistance-rated fire wall and the first floor construction has a fire resistance rating of not less than 1-1/2 hours.
N. Table 601 of the 2000 Edition of the Standard Building Code is hereby amended by adding a new footnote “g” to Table 601.
g. For construction type II, all structural members shall be non combustible
O. Table 602 of the 2000 Edition of the Standard Building Code is hereby amended by adding the following new footnote “d” to Table 602:
d. Mini-warehouse buildings of II construction may have unlimited exterior unprotected wall openings when buildings are spaced a minimum of twenty (20) feet apart and/or twenty (20) feet from a property line when the openings face the property line.
P. Section 704.9 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 704.9 and substituting the following:
704.9 Vertical
separation of openings. Openings in exterior walls in adjacent stories shall
be separated vertically to protect against fire spread on the exterior of the
buildings where the openings are within 5 feet (1524 mm) of each other horizontally
and the opening in the lower story is not a protected opening in accordance
with Section 714.3.7. Such openings shall be separated vertically at least 3
feet (914 mm) by spandrel girders, exterior walls or other similar assemblies
that have a fire-resistance rating of at least 1 hour or by flame barriers that
extend horizontally at least 30 inches (762 mm) beyond the exterior wall. Flame
barriers shall also have a fire-resistance rating of at least 1 hour. The unexposed
surface temperature limitations specified in ASTM E 119 shall not apply to the
flame barriers or vertical separation unless otherwise required by the provisions
of this code.
EXCEPTIONS:
1. This section shall not apply to buildings that are three stories or less in height provided that the openings are separated by a minimum of 24 inches.
2. This section shall not apply to buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. Open parking garages.
Q. Section 705.4 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 705.4 and substituting the following:
705.4 Fire-resistance
rating. Fire walls shall have a fire-resistance rating of not less than four
(4) hours.
EXCEPTION
Attached multiple single-family dwellings (townhouses) not more than three stories
high with separate means of egress and their accessory structures shall be a
2 hours non load bearing (fire wall) or 2 -1 hour load bearing fire walls to
separate single family dwellings from each other. The fire walls shall be fire
rated from both sides of the fire wall.
R. Section 705.5 exception 3 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 705.5 exception 3 and substituting the following:
3. Fire walls shall be permitted to terminate at the interior surface of noncombustible exterior sheathing where the building on each side of the fire wall is protected by an automatic sprinkler system installed in accordance with Section 903.3.1.1.
S. Section 708.1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 708.1 and substituting the following:
708.1 General. Wall assemblies installed as required by Sections 310.3, 402.7.2 and 1004.3.2.1 shall comply with this section. These include:
1. Walls separating dwelling units.
2. Walls separating guestrooms in occupancies in Group R-1 and dwelling units in occupancies of Groups of R-2 and R-4.
3. Walls separating tenant spaces in covered mall buildings.
4. Corridor walls.
5. Walls separating tenant spaces from breezeways exit access shall be installed from the first occupied floor to the roof sheathing and fire rated from both sides in R-I and R-2 occupancies.
T. Section 708.3 of the 2000 Edition of the Standard Building Code is hereby amended by adding a new Section 708.3.1 as follows:
708.3.1. In sprinklered buildings in accordance with Section 903.3.1.1 of a Group A, B, E, & M occupancy, a wall, either full or partial glass, forming a smoke partition may be used in lieu of a required one (1) hour fire resistant wall (tenant separation and corridor walls only) where automatic sprinklers are spaced six (6) feet or less along both sides of the separation wall and not more than one (1) foot away from the glass and so designed that the entire surface of the glass is wet upon activation of the sprinkler system. The wall glass shall be in a gasketed steel frame so installed that the framing system may deflect without breaking (loading) the glass before the sprinkler system operates.
U. Section 708.4 Exceptions 4, 5 and 6 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 708.4 Exceptions 4, 5 and 6 and substituting the following:
4. The fire partition separating tenant spaces in a mall, complying with Section 402.7.2, are not required to extend beyond the underside of a ceiling that is not part of a fire-resistance-rated assembly. A wall is not required in attic or ceiling spaces above tenant separation walls provided a smoke-control system shall be provided where required for atriums in Section 909. Minimum height of 1 hour rated tenant separation wall is 10 feet.
4.1. Tenant separation walls are required to go from the floor to the structural floor/ ceiling or roof/ ceiling assembly in Malls that do not have a smoke control system installed as required by Section 909.
5. Draft stopping is not required at the tenant separation partition in occupancies of Group R-1, R-2 and R-4 that do not exceed four stories in height, the attic space shall be subdivided by draftstops into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling or guest units, whichever is smaller with drafting stopping material on each side of the truss or provide attic draftstopping inline with tenant separation with one layer of draftstopping material.
6. Fireblocking or draftstopping is not required at the tenant separation partitions in buildings equipped with an automatic sprinkler system installed throughout in accordance with Section 903.3.1.1 provided that automatic sprinklers are installed in combustible floor/ceiling and roof/ceiling spaces.
V. Section 715.5.2 Exception 3 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 715.5.2 Exception 3 and substituting the following:
3. Such walls are penetrated by ducted HVAC systems, have a required fire-resistance rating of 1 hour or less, are in areas of other than Group H and are in buildings equipped throughout with an automatic sprinkler system in accordance with section 903.3.1.1.
W. Section 715.5.3.1 Exception 1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 715.5.3.1 Exception 1 and substituting the following:
1. Steel exhaust subducts extend at least 22 inches (559 mm) vertically in an exhaust riser duct installed in a shaft provided there is a continuous airflow upward to the outside.
X. Section 716.4.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 716.4.2 and substituting the following:
716.4.2 Draftstopping shall be provided in attics, mansards, overhangs or other concealed roof spaces of buildings with three or more dwelling or guest units. Draftstopping shall be installed above, and in line with, tenant and dwelling unit separation walls that do not extend to the underside of the roof sheathing above.
EXCEPTIONS:
1. Where corridor walls provide a tenant or dwelling unit separation, draftstopping shall only be required above one of the corridor walls.
2. Attic draftstopping is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
3. In occupancies that do not exceed four stories in height, the attic space shall be subdivided by draftstops into areas not exceeding 3,000 square feet (279 m2) or above every two dwelling units, whichever is smaller with drafting stopping material on each side of the truss or provide attic draftstopping inline with tenant separation with one layer of draftstopping material.
Y. Sections 907.2.10.1.1 through 907.2.10.1.4 of the 2000 Edition of the Standard Building Code are hereby amended by deleting Sections 907.2.10.1.1 through 907.2.10.1.4 and substituting the following:
907.2.10.1.1 Groups R-2, R-3, R-4 and I-1. Single-or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-4 and I-1, regardless of occupant load at all of the following locations:
1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.
2. In each room used for sleeping purposes.
3. In each story within a dwelling unit, including basements, garages and cellars but not including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
Exception: Heat detectors may be substituted for smoke detectors installed in cellars and attached garages.
907.2.10.1.2 Additions, alterations or repairs to Group R. Where an addition, alteration or repair to an individual dwelling unit or guestroom in Group R requires a permit, smoke alarms shall be installed within that individual dwelling unit or guestroom in accordance with this section. Where one or more sleeping rooms are added or created in an existing Group R, smoke alarms shall be installed in accordance with this section.
EXCEPTION: Repairs to the exterior surfaces of occupancies in Group R are exempt from the requirements of this section.
Z. Table 1003.2.3 footnote “a” of the 2000 Edition of the Standard Building Code are hereby amended by deleting the footnote “a” of Table 1003.2.3 and substituting the following:
{a} Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
AA. Section 1003.2.12.1 and Section 1003.2.12.2 of the 2000 Edition of the Standard Building Code are hereby amended by deleting Section 1003.2.12.1 and Section 1003.2.12.2 and substituting the following:
1003.2.12.1 Height. Guards shall form a protective barrier not less than 42 inches (1067 mm) high, measured vertically above the leading edge of the tread, adjacent walking surface or adjacent seatboard.
EXCEPTIONS:
1. The top element of a guard at the inside open or unenclosed edge of any intermediate stairway landing where the stairs reverse direction may be at the same height as the stairway handrails when the horizontal distance between the stair flights is 1 ft (305mm) or less and when a continuous handrail as specified in Section 1003.3.3.11.4 is provided.
2. Guards whose top rail also serves as a handrail shall have a height not less than 34 inches (864 mm) and not more than 38 inches (965 mm) measured vertically from the leading edge of the stair tread nosing.
1003.2.12.2 Opening limitations. Open guards shall have balusters or ornamental patterns such that a 4-inch-diam-eter (102 mm) sphere cannot pass through any opening up to a height of 34 inches (864 mm). From a height of 34 inches (864 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, a sphere 8 inches (203 mm) in diameter shall not pass. A bottom rail or curb shall be provided that a 2-inch (51.5 mm) in diameter sphere can not pass
EXCEPTIONS:
1. The triangular openings formed by the riser, tread and bottom rail at the open side of a stairway shall be of a maximum size such that a sphere of 6 inches (152 mm) in diameter cannot pass through the opening.
2. At elevated walking surfaces for access to and use of electrical, mechanical, or plumbing systems or equipment, guards shall have balusters or be of solid materials such that a sphere with a diameter of 21 inches (533 mm) cannot pass through any opening.
3. In occupancies in Group I-3, F, H or S, balusters, horizontal intermediate rails or other construction shall not permit a sphere with a diameter of 21 inches (533 mm) to pass through any opening.
4. In assembly seating areas, guards at the end of aisles where they terminate at a fascia of boxes, balconies, and galleries shall have balusters or ornamental patterns such that a 4-inch-diameter (102 mm) sphere cannot pass through any opening up to a height of 26 inches (660 mm). From a height of 26 inches (660 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, a sphere 8 inches (203 mm) in diameter shall not pass.
AB. Section 1004.2.2.1 Exception 2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 1004.2.2.1 Exception 2 and substituting the following:
2. Where a building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 the separation distance of the exit doors or exit access doorways shall not be less than one-third of the length of the maximum overall diagonal dimension of the area served.
AC. Table 1004.2.4 footnote “b” of the 2000 Edition of the Standard Building Code is hereby amended by deleting the footnote “b” of Table 1004.2.4 and substituting the following:
{b} Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
AD. Table 1004.3.2.1 footnote “c” of the 2000 Edition of the Standard Building Code is hereby amended by deleting the footnote “c” of Table 1004.3.2.1 and substituting the following:
{c} Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1.
AE. Footnote “c” of Table 1005.2.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting footnote “c” of Table 1005.2.2 substituting the following:
{c} Buildings classified as Group R-2 equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and provided with emergency escape and rescue openings in accordance with Section 1009 shall have a maximum height of three stories above grade.
AF. Section 1009.1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 1009.1 and substituting the following:
1009.1 Every sleeping
room on the first, second, third and forth story or within basements of Group
R occupancies shall have at least one operable window or exterior door approved
for emergency egress or rescue.
Exceptions:
1. Group R1 occupancies equipped with an approved automatic sprinkler system
in accordance with Section 903.3.1.1.
2. Group R1 occupancies with sleeping rooms provided with a door to a rated
corridor or balcony having access to two remote exits in opposite directions.
3. The emergency escape and rescue opening may open onto a balcony within an
atrium provided the balcony provides access to an exit and the dwelling unit
or sleeping room has a means of egress which is not open to the atrium.
AG. Section 1503.4.1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 1503.4.1 and substituting the following:
1503.4.1 Gutter and Leaders. All buildings shall be provided with adequate gutters and leaders of a non-combustible material or a minimum of schedule 40 plastic pipe. See Chapter 11 of the Standard Plumbing Code for sizing of vertical leaders and horizontal storm drains. All leaders shall be terminated in an approved storm drain or storm sewer system where such is available. Where a public storm sewer system is not available, adequate provision shall be made by the owner for the disposal of all storm water.
1503.4.2. Where leaders and storm drains are required along a public right of way adjacent to public sidewalks or paved public walkways, the discharge from such leaders shall be piped under such sidewalk or paved public walkway to the nearest storm sewer or sidewalk curb. No storm water shall be discharged in such a manner as will permit it to flow over or across any public sidewalk or paved public right of way area.
AH. Section 2109.4.3 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 2109.4.3 and substituting the following:
2109.4.3 Lateral support. Lateral support shall be provided by intersecting walls, pilasters, columns, or other vertical members of sufficient strength to provide the required support when the distance between supports is measured horizontally; or by floors, roofs or other horizontal structural elements which are of sufficient strength to provide the required support when the distance between supports is measured vertically.
2109.4.3.1 Sufficient bonding or anchorage shall be provided between the walls and their supports to resist the assumed wind or other horizontal forces acting either inward or outward. All structural elements relied upon for lateral support shall have sufficient strength and stability to transfer the horizontal force acting in either direction to adjacent structural members or to the ground. When floors or roofs are depended upon for receiving horizontal forces, provisions shall be made in the buildings to transfer the lateral forces to the ground.
2109.4.3.2 When horizontal structural elements of a building (such as floors, roof spandrel beams) are depended upon for lateral support, vertical bracing of bearing or nonbearing wall shall also be provided at intervals of not more than 75 times the wall thickness. Such vertical bracing may be provided by cross walls, pilasters, buttresses or other equivalent structural members.
2109.4.3.3 PILASTERS. When relied upon to provide the required lateral support, the width of pilasters shall not be less than 1/10 the spaces between such pilasters. All pilasters shall not be less than 4 inches (102 mm) thicker than the wall supported. In no case shall the distance between such pilasters exceed the lateral support provisions of Table 2109.4.1.
2109.4.3.4 PIERS.
The unsupported height of masonry piers shall not exceed 10 times their least
dimension. When structural clay tile or hollow concrete masonry units are used
for isolated piers to support beams and girders, the cellular spaces shall be
filled solidly with concrete or Type M or S mortar, except that unfilled hollow
piers may be used if their unsupported height is not more than four times their
least dimension. When hollow masonry units are solidly filled with concrete
or Type M, S or N mortar, the allowable compressive stress may be increased
as provided for in Table 2109.3.2.
2109.4.3.5 Hollow piers shall be capped with 4 inches (102 mm) of solid masonry
or concrete or shall have cavities of top course filled with concrete or grout
or other methods approved by the Building Official.
AI. Section 2308.9.1 and Table 2308.9.1 of the 2000 Edition of the Standard Building Code are amended by deleting Section 2308.9.1 and Table 2308.9.1 and substituting the following:
2308.9.1. Studs in one and two story buildings shall not be less than 2 X 4 with the wide face perpendicular to the wall. In three story buildings, studs in first story shall not be less than 2 X 4s @ 12 in. o.c., 3 X 4s or 2 X 6s. Studs shall be spaced in accordance with Table 2308.9.1.
TABLE 2308.9.1
SIZE, HEIGHT AND SPACING OF WOOD STUDS
StudSize BEARING WALLS NON BEARING WALLS
Lateral unsupported stud height{a}(ft) SupportingRoof andCeilingOnly (in) Supporting1
floor, roofand ceiling(in) Supporting2 floors,roof andceiling (in) LateralUnsupported
stud height{a}(ft) Spacing(in)
2X3{b} 10 16
2X4 10 24 16 12 14 24
3X4 10 24 24 16 14 24
2X5 10 24 24 -- 16 24
2X6 10 24 24 16 20 24
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
{a} Listed heights are distances between points of lateral support placed perpendicular to the plane of the wall. Increases in unsupported height are permitted where justified by an analysis.
{b} Shall not be used in exterior walls.
AJ. Footnotes e and f of Table 2902.1 of the 2000 Edition of the Standard Building Code are hereby amended by deleting footnotes e and f of Table 2902.1 and substituting the following:
{e} For day nurseries,
a minimum of one bathtub shall be required.
{f} The minimum number of service sinks shall be 1 per building or 1 per janitor’s
closet or 1 per tenant space over 7,500 gross square feet.
AK. Section 2902.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 2902.2 and substituting the following:
2902.2 Separate
facilities. Where plumbing fixtures are required, separate facilities shall
be provided for each sex.
EXCEPTIONS:
1. Separate facilities shall not be required for private facilities.
2. Separate facilities shall not be required in structures or tenant spaces with a total gross square footages in the following occupancies.
Table 403.2 Occupancies
with one bathroom for both sexes.
Occupancy Gross Square footage
Business 1,500
Education 1,500
Factory 3,000
Mercantile 2,000
Pools 1,000
Restaurants 1,000
Storage 7,500
EXCEPTION: Any business that dispenses gasoline or diesel oil to the public shall have separate facilities for each sex.
AL. Section 2902.4 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 2902.4 and substituting the following:
2902.4 Location of employee toilet facilities in occupancies other than assembly or mercantile. Access to toilet facilities in occupancies other than mercantile and assembly occupancies shall be from within the employees' regular working area. Employee facilities shall be either separate facilities or combined employee and public customer facilities. Minimum employee facilities are 1 water closet, 1 lavatory and 1 drinking fountain.
EXCEPTION:
1. Facilities that are required for employees in storage structures or kiosks,
and are located in adjacent structures under the same ownership, lease or control,
shall be a maximum travel distance of 500 feet (152 m) from the employees' regular
working area.
2. In education occupancies, the maximum travel distance to bathrooms shall
be 300 ft and the facilities shall be located on the same floor level.
2902.4.1 Travel distance. The required toilet facilities in occupancies other than assembly or mercantile shall be located not more than one story above or below the employee's regular working area and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).
EXCEPTION: The location and maximum travel distances to the required employee toilet facilities in factory and industrial occupancies are permitted to exceed that required in Section 2902.4.1, provided the location and maximum travel distances are approved by the code official.
AM. Section 2902.6 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 2902.6 and substituting the following:
2902.6 Public facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilities and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). The path of travel to the public facilities shall not pass through a stock room or similar room.
2902.6.1 Covered malls. In covered mall buildings, the path of travel to required toilet facilities shall not exceed a distance of 300 feet (91 440 mm). The required facilities shall be based on total gross square footage, and facilities shall be installed in each individual store or in central toilet areas located in accordance with this section. Restaurants other than food tenants in the food court shall have the required facilities installed within their tenant space. The maximum travel distance to the central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space.
2902.6.2 Pay facilities. Required facilities shall be free of charge and designated by legible signs for each sex. Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities.
2902.6.3 Public
lavatories. In employee and public toilet rooms, the required lavatory shall
be located in the same room as the required water closet.
Exception. Educational occupancies
2902.6.4 Unisex toilet and bathing rooms. In assembly and mercantile occupancies, an accessible unisex toilet room shall be provided where an aggregate of six or more male or female water closets are required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the unisex toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible unisex bathing room shall be provided.
2902.6.4.1 Standard. Unisex toilet and bathing rooms shall comply with Section 404 of the Standard Plumbing Code and ICC/ANSI A117.1
AN. Section 3103 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3103 and substituting the following:
3103
TEMPORARY STRUCTURES
3103.1 General. The provisions of this section shall apply to structures erected for a period of 90 days or less. Tents and other membrane structures erected for a period of 90 days or less shall comply with the Metropolitan Fire Code. Those erected for a longer period of time shall comply with applicable sections of this code.
EXCEPTION: Provisions of the Metropolitan Fire Code shall apply to tents and membrane structures erected for a period of 90 days or less.
3103.1.1 Permit required. Temporary structures that cover an area in excess of 120 square feet (11.16 m2), including connecting areas or spaces with a common means of egress or entrance which are used or intended to be used for the gathering together of ten or more persons, shall not be erected, operated or maintained for any purpose without obtaining a permit from the building official.
AO. Section 3109.4.1.8 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3109.4.1.8 in its entirety.
AP. Section 3202.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3202.2 and substituting the following:
3202.2 Encroachments above grade and below 8 feet in height. Encroachments into the public right-of-way above grade and below 8 feet (2438 mm) in height shall be prohibited. Doors and windows shall not open or project into the public right-of-way above grade and below 8 feet in height.
3202.2.1 Awnings, canopies, marquees and signs. The vertical clearance from the public right-of-way sidewalk to the lowest part of any awning, canopies, marquees and signs, shall be 8 feet (2438 mm) minimum.
AQ. Section 3202.3.1 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3202.3.1 and substituting the following:
3202.3.1 Awnings, canopies, marquees and signs. Awnings, canopies, marquees and signs shall be constructed so as to support applicable loads as specified in Chapter 16. Awnings, canopies, marquees and signs with less than 15 feet (4572 mm) clearance above the sidewalk shall not extend into or occupy more than two-thirds the width of the sidewalk measured from the building.
3202.3.1.1 SUPPORT. Fixed awnings, marquees, signs or canopies shall be entirely supported from the building.
AR. Section 3202.4 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3202.4 and substituting the following:
3202.4 Temporary encroachments. Where allowed by the local authority having jurisdiction, vestibules and storm enclosures shall not be erected for a period of time exceeding 90 days in any one year and shall not encroach more than 3 feet (914 mm) nor more than one-fourth of the width of the sidewalk beyond the street lot line. Temporary entrance awnings shall be erected with a minimum clearance of 8 feet (2438 mm) to the lowest portion of the hood or awning where supported on removable steel or other approved noncombustible support from the building.
AS. Section 3409 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 3409 in its entirety.
AT. Section D101.2 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section D101.2 and substituting the following:
D101.2 The Fire District shall include such territory or portion thereof as established by the official Fire Zone Map of the Metropolitan Government of Nashville and Davidson County, Tennessee.’’
Section 15. Section 16.08.016 of the Metropolitan Code of Laws is hereby amended by deleting the section in its entirety and substituting the following:
“ENERGY CODE SECTION
"16.08.016 Amendments to the Energy Code
A. Section 101.4.1 of the 2000 Edition of the International Energy Conservation Code is hereby amended by adding new sections as follows:
101.4.1.3 Buildings and structures used as nonresidential farm building.
101.4.1.4 Temporary buildings used exclusively for construction purposes.
101.4.1.5. Additions to one and two family dwellings which:
A. Are less than
ten percent (10%) of the square footage of the dwelling and;
B. Have more than fifty percent (50%) of the total outside wall and roof space
composed of glass."
PLUMBING CODE SECTION
Section 16. Section 16.12.120 of the Metropolitan Code of Laws is hereby amended by deleting Section 16.12.120 and substituting the following:
"16.12.120 Adoption by reference
A. The following sections and appendices of the 2000 Edition of the Standard Plumbing Code are adopted and incorporated into this chapter as the technical section of the Plumbing Code of the Metropolitan Government, by reference, as fully as though copied into this code, except as such sections and appendices have been or may be hereafter revised or amended by the Metropolitan Council: Section 201 through Chapter 13 inclusive, Appendices B, C, D, E, and G.
B. The following sections of the Subsurface Sewage Disposal System laws and regulations as published by the Tennessee Department of Environment and Conservation, Ground Water Protection division, as amended October 1993, are adopted and incorporated into this chapter as the Plumbing Code of the Metropolitan Government, by reference, as fully as though copied in this chapter, except as such sections and appendices have been or may be hereafter revised or amended by the Metropolitan Council: Section 1200-1-6.01 through 1200-1-1.13 and 1200-1-6-.20, 1200-1-6-.22 and Appendices I and II." See Chapter 15.72 of the Metropolitan Code of Laws for additional requirements.’’
Section 17. Section 16.12.130 of the Metropolitan Code of Laws is amended by deleting Section 16.12.130 and substituting the following:
16.12.130 Amendments
to the Standard Plumbing Code
The following amendments, deletions, or additions to the 2000 Edition of the
Standard Plumbing Code are adopted by reference, as fully as though copied into
such Plumbing Code, and thereby made a part of the Plumbing Code.
A. Section 201 of the 2000 Edition of the Standard Plumbing Code is amended by adding a new Section 201.5 and substituting the following:
201.5 Interchangeability with the Standard Codes. The International Building Code shall be construed to mean the Standard Building Code. The International Property Maintenance Code shall be construed to mean the Property Standards Code of the Metropolitan Government. The International Mechanical Code shall be construed to mean the Standard Mechanical Code. The International Fuel Gas Code shall be construed to mean the Standard Gas Code. The International Plumbing Code shall be construed to mean the Standard Plumbing Code. The International Private Sewage Disposal Code shall be construed to mean the Subsurface Sewage Disposal Systems Code The ICC Electrical Code shall be construed to mean the National Electrical Code.
B. Section 202 of the 2000 Edition of the Standard Plumbing Code is hereby amended by adding the definition of "Plumbing Official" as follows:
PLUMBING OFFICIAL--shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
C. Sections 305.6 and 305.6.1 of the 2000 Edition of the Standard Plumbing Code are hereby amended by deleting Sections 305.6 and 305.6.1 and substituting the following:
305.6 Freezing. Plumbing fixtures, water, soil and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperature unless adequate provision is made to protect such pipes from freezing by insulation and heat or in the case of plumbing fixtures, if the manufacturer provides guidelines for exterior use. Exterior water supply system piping shall be installed not less than twenty –four (24) inches below grade.
305.6.1 Sewer depth. Building sewers that connect to private sewage disposal systems shall be a minimum of twelve (12) inches below finished grade at the point of septic tank connection. Building sewers shall be a minimum of twelve (12) inches below grade. Sewers subject to vehicular traffic require a minimum of twenty-four (24) inches of cover or shall be encased radially in six inches (6) of concrete. A sleeve shall be required to protect the service pipe from the cement encasement in compliance with Section 305.1 Corrosion.
D. Section 305.8 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 305.8 and substituting the following:
305.8 Protection against physical damage. In concealed locations where piping, other than cast-iron or galvanized steel, is installed through holes or notches in studs, joists, rafters or similar members less than 1.5 inches (38 mm) from the nearest edge of the member, the pipe shall be protected by shield plates. Protective shield plates shall be a minimum of 0.062-inch-thick (1.6 mm) steel, shall cover the area of the pipe where the member is notched or bored, and shall extend a minimum of 2 inches (51 mm) above sole plates and a minimum of 2 inches (51 mm) below top plates.
E. Section 307 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 307 and substituting the following:
SECTION 307
STRUCTURAL SAFETY
307.1 General. In the process of installing or repairing any part of a plumbing and drainage installation, the finished floors, walls, ceilings, tile work or any other part of the building or premises that must be changed or replaced shall be left in a safe structural condition in accordance with the requirements of the Standard Building Code.
307.2 Penetrations of floor-ceiling assemblies and fire-resistance-rated assemblies. Penetrations of floor-ceiling assemblies and assemblies required to have a fire-resistance rating shall be protected in accordance with the Standard Building Code.
307.3 Trench location. Trenches installed parallel to footings shall not extend below the 45-degree (0.79 rad) bearing plane of the footing or wall.
307.4.1. Cutting, notching and boring in wood members. Joist notching. Notches on the ends of joists shall not exceed one-fourth the actual joist depth. Holes bored in joists shall not be within 2 inches (51 mm) of the top or bottom of the joist, and the diameter of any such hole shall not exceed one third the actual depth of the joist. Notches in the top or bottom of joists shall not exceed one sixth of the actual joist depth and shall not be located in the middle third of the span.
307.4.2. Stud cutting and notching. In exterior walls and bearing partitions, any wood stud is permitted to be cut or notched to a depth not exceeding 25 percent of its actual width. Cutting or notching of studs to a depth not greater than 40 percent of the width of the actual stud width is permitted in nonbearing partitions supporting no loads other than the weight of the partition.
307.4.3. Bored holes. A hole not greater in diameter than 40 percent of the actual stud width is permitted to be bored in any wood stud. Bored holes not greater than 60 percent of the actual width of the stud is permitted in nonbearing partitions or in any wall where each bored stud is doubled, provided not more than two such successive doubled studs are so bored. In no case shall the edge of the bored hole be nearer than 0.625 inch (15.9 mm) to the edge of the stud. Bored holes shall not be located at the same section of stud as a cut of notch.
307.5.1 Cutting, notching and boring holes in structural steel framing. The cutting, notching and boring of holes in structural steel framing members shall be as prescribed by the registered design professional.
307.5.2. Cutting, notching and boring holes in cold-formed steel framing. Flanges and lips of load-bearing cold-formed steel framing members shall not be cut or notched. Holes in webs of load-bearing cold-formed steel framing members shall be permitted along the centerline of the web of the framing member and shall not exceed the dimensional limitations, penetration spacing or minimum hole edge distance as prescribed by the registered design professional. Cutting, notching and boring holes of steel floor/roof decking shall be as prescribed by the registered design professional.
307.5.3. Cutting, notching and boring holes in nonstructural cold-formed steel wall framing. Flanges and lips of nonstructural cold-formed steel wall studs shall not be cut or notched. Holes in webs of nonstructural cold-formed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 1.5 inches (38 mm) in width or 4 inches (102 mm) in length, and the holes shall not be spaced less than 24 inches (610 mm) center to center from another hole or less than 10 inches (254 mm) from the bearing end.
F. Section 312.6 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 312.6 in its entirety.
G. Chapter 3 of the 2000 Edition of the Standard Plumbing Code is hereby amended by adding a new Section 315 as follows:
SECTION 315
BASIC PRINCIPLES
The basic principles of this Code are enunciated as basic goals in environmental sanitation worthy of accomplishment through properly designed, acceptably installed, and adequately maintained plumbing systems. Some of the details of plumbing construction must vary, but the basic sanitary and safety principles are the same. The principles may serve to define the intent.
315.1 Principle
No.1
All buildings, structures and premises intended for human habitation, occupancy,
use for employment; or the preparation or processing of food, drinks or other
materials for human consumption shall be provided with an adequate, safe and
potable water supply through a safe system of piping to all fixtures, appliances,
appurtenances, etc.
315.2 Principle
No. 2
Every building having plumbing fixtures installed and intended for human habitation,
occupancy, or use on premises abutting on a street, alley, or easement in which
there is a public sewer shall have a separate connection with the sewer.
315.3 Principle
No. 3
A dwelling type building provided with a drainage system, a public sewer connection
or a private sewage disposal system, shall have at least one water closet, one
bathtub or shower, one lavatory, one kitchen?type sink, and an adequate source
of hot water, for each family unit to meet minimum basic requirements for health,
sanitation and personal hygiene. Water heating facilities shall be accessible
for emergency maintenance without entering any individual apartment or living
unit, except that water heaters may be located within an apartment or living
unit when supplying hot water to that unit only.
All other buildings, structures, or premises intended for human occupancy or use shall be provided with adequate sanitary facilities as may be required, but not less than one water closet and one hand washing lavatory.
315.4 Principle
No. 4
Plumbing fixtures shall be made of smooth nonabsorbent material, shall be free
from concealed fouling surfaces, and shall be located in ventilated enclosures.
315.5 Principle
No. 5
Each fixture directly connected to the drainage system shall be equipped with
a water?seal trap.
315.6 Principle
No. 6
No substance which will clog the pipes, produce explosive mixtures, destroy
the pipes or their joints, or interfere unduly with the sewage?disposal process
shall be allowed to enter the building drainage system.
315.7 Principle
No. 7
Proper protection shall be provided to prevent contamination of food, water,
sterile goods, and similar materials by backflow of sewage. When necessary,
the fixture, device, or appliance shall be connected indirectly with the building
drainage system.
315.8 Principle
No. 8
No water closet shall be located in a room or compartment which is not properly
lighted and ventilated.
315.9 Principle
No. 9
If water closets or other plumbing fixtures are installed in buildings where
there is no sewer within a reasonable distance, suitable provision shall be
made for disposing of the building sewage by some accepted method of sewage
treatment and disposal.
315.10 Principle No. 10
Where a plumbing drainage system may be subject to backflow of sewage, suitable
provisions shall be made to prevent its overflow in the building.
315.11 Principle
No. 11
Plumbing shall be installed with due regard to preservation of the strength
of structural members and prevention of damage to walls and other surfaces through
fixture usage.
315.12 Principle
No. 12
Sewage or other waste, from a plumbing system, which may be deleterious to surface
or subsurface waters shall not be discharged into the ground or into any waterway
unless it has first been rendered innocuous through subjection to some acceptable
form of treatment.
315.13 Principle
No. 13
All plumbing fixtures, devices, appliances, and appurtenances shall be adequately
supplied with water in sufficient volume and pressure to enable them to function
properly.
315.14 Principle
No. 14
The pipes conveying water to plumbing fixtures, appliances, devices and appurtenances
shall be of sufficient size as to supply water at rates that will prevent undue
pressure drops at any one fixture, when any other fixture, appliance, device
or appurtenance, or group, is being flushed, operated or used.
315.15 Principle
No. 15
There shall be no direct or indirect cross connections, either existing or potential,
between a safe potable water supply and an unsafe, non potable supply.
315.16 Principle
No. 16
Adequate protection shall be provided to prevent possible backflow or back siphonage
of an unsafe or potentially hazardous fluid or material into a safe water system.
315.17 Principle
No. 17
The piping and connections of the plumbing system shall be of durable materials,
free from defects in workmanship and materials, and systems shall be designed
and constructed to provide adequate service for a reasonable life under stresses
imposed by structural loading, temperature variation, vibration and other conditions.
315.18 Principle
No. 18
Devices for heating and storing water shall be designed and installed to prevent
all danger from overheating and explosion and to prevent undue flow of hot water
or steam into the cold water supply pipes.
315.19 Principle
No. 19
Refrigerators, coolers, receptacles, sterilizers, vats, and similar equipment
used for storing or holding foods, beverages, sterile goods and water conditioning
equipment, etc., shall discharge into the building drainage system through an
indirect waste.
315.20 Principle
No. 20
Water closets, bathtubs, showers, urinals and similar fixtures shall be suitably
enclosed and screened for privacy.
315.21 Principle
No. 21
Plumbing systems, including fixtures, shall be maintained in sanitary condition
and proper working order.
315.22 Principle
No. 22
Sewage and wastes from plumbing and drainage systems shall be adequately treated
and disposed of in accordance with the requirements of the Plumbing Official.
H. Footnotes e and f of Table 403.1 of the 2000 Edition of the Standard Plumbing Code are hereby amended by deleting footnotes e and f of Table 403.1 and substituting the following:
{e} For day nurseries,
a minimum of one bathtub shall be required.
{f} The minimum number of service sinks shall be 1 per building or 1 per janitor’s
closet or 1 per tenant space over 7,500 gross square feet.
I. Section 403.2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 403.2 and substituting the following:
403.2 Separate
facilities. Where plumbing fixtures are required, separate facilities shall
be provided for each sex.
EXCEPTIONS:
1. Separate facilities shall not be required for private facilities.
2. Separate facilities shall not be required in structures or tenant spaces with a total gross square footages in the following occupancies.
Table 403.2 Occupancies
with one bathroom for both sexes.
Occupancy Gross Square footage
Business 1,500
Education 1,500
Factory 3,000
Mercantile 2,000
Pools 1,000
Restaurants 1,000
Storage 7,500
EXCEPTION: Any business that dispenses gasoline or diesel oil to the public shall have separate facilities for men and female.
J. Section 403.4 of the 2000 Edition of the Standard Building Code is hereby amended by deleting Section 403.4 and substituting the following:
403.4 Location
of employee toilet facilities in occupancies other than assembly or mercantile.
Access to toilet facilities in occupancies other than mercantile and assembly
occupancies shall be from within the employees' regular working area. Employee
facilities shall be either separate facilities or combined employee and public
customer facilities. Minimum employee facilities are 1 water closet, 1 lavatory
and 1 drinking fountain.
EXCEPTION:
1. Facilities that are required for employees in storage structures or kiosks,
and are located in adjacent structures under the same ownership, lease or control,
shall be a maximum travel distance of 500 feet (152 m) from the employees' regular
working area.
2. In education occupancies, the maximum travel distance to bathrooms shall
be 300 ft and the facilities shall be located on the same floor level.
403.4.1 Travel distance. The required toilet facilities in occupancies other than assembly or mercantile shall be located not more than one story above or below the employee's regular working area and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m).
EXCEPTION: The location and maximum travel distances to the required employee toilet facilities in factory and industrial occupancies are permitted to exceed that required in 403.4.1, provided the location and maximum travel distances are approved by the code official.
K. Section 403.6 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 403.6 and substituting the following:
403.6 Public facilities. Customers, patrons and visitors shall be provided with public toilet facilities in structures and tenant spaces intended for public utilization. Public toilet facilities shall be located not more than one story above or below the space required to be provided with public toilet facilities and the path of travel to such facilities shall not exceed a distance of 500 feet (152 m). The path of travel to the public facilities shall not pass through a stock room or similar room.
403.6.1 Covered malls. In covered mall buildings, the path of travel to required toilet facilities shall not exceed a distance of 300 feet (91 440 mm). The required facilities shall be based on total gross square footage, and facilities shall be installed in each individual store or in central toilet areas located in accordance with this section. Restaurants other than food tenants in the food court shall have the required facilities installed within their tenant space. The maximum travel distance to the central toilet facilities in covered mall buildings shall be measured from the main entrance of any store or tenant space.
403.6.2 Pay facilities. Required facilities shall be free of charge and designated by legible signs for each sex. Where pay facilities are installed, such facilities shall be in excess of the required minimum facilities.
L. Section 405.3.3 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 405.3.3 and substituting the following:
405.3.3 Public
lavatories. In employee and public toilet rooms, the required lavatory shall
be located in the same room as the required water closet.
Exception. Educational occupancies
M. Section 406.2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 406.2 in its entirety.
N. Section 409.2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 409.2 and substituting the following:
409.2 Water connection. The water supply to a commercial dishwashing machine shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.
O. Section 410.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 410.1 and substituting the following:
410.1 Approval. Drinking fountains shall conform to ASME A112.19.1, ASME A112.19.2 or ASME A112.19.9, and water coolers shall conform to ARI 1010. Where water is served in restaurants, drinking fountains shall not be required.
P. Section 411.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 411.1 and substituting the following:
411.1 Water connection. Emergency showers and eyewash stations shall be provided with an unvalved supply of cold water as required by the manufacturer.
Q. Section 412.3 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 412.3 and substituting the following:
412.3 Size of floor drains. Floor drains shall have a minimum 3-inch-diameter (76 mm) drain outlet.
R. Section 420 of the 2000 Edition of the Standard Plumbing Code is hereby amended by adding a new Section 420.5 as follows:
420.5 Surrounding material. Walls within 2 feet (610 mm) of a water closet shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet (1219 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture.
S. Section 423.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 423.1 and substituting the following:
423.1 Water connections. Baptisteries, ornamental and lily pools, aquariums, ornamental fountain basins, swimming pools, and similar constructions, where provided with water supplies, shall be protected against backflow in accordance with 608. Provide back flow preventer if the fill spout is not provided with an air gap.
T. Section 425 of the 2000 Edition of the Standard Plumbing Code is hereby amended by adding a new Section 425.2.
425.2 Access to concealed connections. Fixtures with concealed slip-joint connections shall be provided with an access panel or utility space at least 12 inches (305 mm) in its smallest dimension or other approved arrangement so as to provide access to the slip connections for inspection and repair.
U. Section 501.2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 501.2 and substituting the following:
501.2 Water heater as space heater. Where a combination potable water heating and space heating system requires water for space heating at temperatures higher than 140ºF (60ºC), a tempering valve shall be provided to limit the water supplied to the potable hot water distribution system to a temperature of 120ºF. The potability of the water shall be maintained throughout the system.
V. Section 503.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 503.1 and substituting the following:
503.1 Cold water line valve. The cold water branch line from the main water supply line to each hot water storage tank or water heater shall be provided with a valve, located within 3 feet of the equipment and serving only the hot water storage tank or water heater. The valve shall not interfere or cause a disruption of the cold water supply to the remainder of the cold water system. The valve shall be provided with access on the same floor level as the water heater served.
W. Section 504.7.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 504.7.1 and substituting the following:
504.7.1 Pan size and drain. The pan shall be not less than 2.0 inches (51 mm) deep and shall have a minimum clearance from the water heater of two (2) inches on all sides: the pan shall be of sufficient size and shape to receive all dripping or condensate from the tank or water heater. The pan shall be drained by an indirect waste pipe having a minimum diameter of 1 inch.
X. Section 606.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 606.1 and substituting the following:
606.1 Location
of full-open valves. Full-open valves shall be installed in the following locations:
The main shut off valve is required to be installed in the habitable or occupied
portion of the structure.
1. On the building water service pipe from the public water supply near the
curb.
2. On the water distribution supply pipe at the entrance into the structure.
3. On all branches.
4. On the base of every water riser pipe in occupancies other than multiple
family residential occupancies that are two stories or less in height.
5. On the top of every water down-feed pipe in occupancies other than one-and
two-family residential occupancies.
6. On the entrance to every water supply pipe to a dwelling unit, except where
supplying a single fixture equipped with individual stops.
7. On the water supply pipe to a gravity or pressurized water tank.
8. On the water supply pipe to every water heater.
Y. Section 606.2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 606.2 and substituting the following:
606.2 Location
of shutoff valves. Shutoff valves shall be installed in the following locations:
1. On the fixture supply to each plumbing fixture except tubs and showers in
other than one-and two-family residential occupancies, and other than in individual
guestrooms that are provided with unit shutoff valves in hotels, motels, boarding
houses and similar occupancies.
2. On the water supply pipe to each sillcock.
3. On the water supply pipe to each appliance or mechanical equipment.
Z. Footnotes Table 710.1(1) of the 2000 Edition of the Standard Plumbing Code are hereby amended by adding footnote b to Table 710.1(1):
{b} There shall be 3 water closets maximum on any 3 inch drain line.
AA. Section 903.1 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 903.1 and substituting the following:
903.1 Stack required. Every building in which plumbing is installed shall have at least one 3 inch main vent stack. Such stack shall run undiminished in size and as directly as possible from the building drain through to the open air or to a vent header that extends to the open air.
AB. Section 608.16.4 Exception 2 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Section 608.16.4 exception 2 in its entirety.
AC. Chapter 12 of the 2000 Edition of the Standard Plumbing Code is hereby amended by deleting Chapter 12 in its entirety.
AD. The 2000 Edition of the Standard Plumbing Code is hereby amended by adding Appendix H as follows:
APPENDIX H REGULATIONS
GOVERNING PRIVATE
SEWAGE DISPOSAL SYSTEMS
The following regulations shall apply to the manufacture, sale, installation, repair, alteration, extension and relocation of all private sewage disposal systems under the jurisdiction of the Metropolitan Government of Nashville and Davidson County.
H101. APPROVED AND LIMITATIONS.
H101.1 ALLOWABLE USE. Septic tanks and soil absorption systems and other similar facilities may be constructed where no public sewerage system is available or is likely to become available within a reasonable time.
H101.2 PUBLIC SEWER CONNECTION. Private domestic sewage treatment and disposal systems shall be discontinued and adequately abandoned when public sewers become available to the building served.
H101.3 PERMISSION TO CONSTRUCT. No plumbing permit shall be issued for the installation of any septic tank or disposal field or for any individual or private sewage disposal system until satisfactory evidence of approval of such system, by the Metropolitan Department of Health, has been submitted to the Department of Codes Administration. On approved and recorded subdivisions, such notification consists of a letter to Codes Administration from the Health Department which covers each subdivided lot.
H101.4 PLANS AND SPECIFICATIONS.
H101.4.1 All manufacturers or distributors of mechanical sewage disposal units, filters, precast septic tanks or any other method of sewage disposal must submit detailed plans and specifications to the Director of Health of the Metropolitan Health Department, and receive approval prior to the manufacture and sale or installation of the product with the Metropolitan area of Nashville and Davidson County.
H101.4.2 Commercial and public buildings, such as but not limited to theaters, food dispensers, assembly halls, schools, churches, apartment buildings, motels, factories, mobile home parks, camp grounds and parks proposed to be constructed in an unsewered area, must submit detailed plans and specifications for the proposed sewage disposal system to the Sanitary Engineering Division of the Metropolitan Health Department for approval prior to any construction.
H101.4.3 The plans and specifications shall be submitted in triplicate and shall include the following:
H101.4.3.1 Detailed plan of the proposed septic tank or treatment tank and effluent disposal system showing building location, and with the distance labeled from building served to system, from system to well, lot line, lake, stream or other watercourse.
H101.4.3.2 The ground slope should be indicated and information submitted relative to the expected use and occupancy of the building to be served.
H101.4.3.3 Provide soil borings and percolation test data.
H101.4.3.4 There shall be maintained at the project site one set of plans bearing the Health Department's stamp of approval.”
GAS CODE SECTION
Section 18. Sections 16.16.190B, C, D and E of the Metropolitan Code of Laws are hereby amended by deleting Sections 16.16.190B, C, D and E and substituting the following:
“16.16.190 Certain supplemental codes and standards adopted by reference.
B. The 2000 Edition
of the Standard Gas Code, Sections 201 through Chapter 7 inclusive and Appendixes
A, B, C, and D;
C. The 1998 Edition of the Standard for the Storage and Handling of Liquified
Petroleum Gases (NFPA 58), Sections 1-1 through 9-5.6 and Chapter 12, inclusive
with Appendixes A, B, C, D, E, F, G, H and I:
D. The 2000 Edition of the Standard Mechanical Code, Sections 201 through Chapter
15 inclusive with Appendix A;”
Section 19. Sections 16.16.200, 16.16.210 and 16.16.220 of the Metropolitan Code of Laws are hereby amended by deleting Sections 16.16.200, 16.16.210 and 16.16.220 in their entirety.
Section 20. Section 16.16.240 of the Metropolitan Code of Laws is hereby amended by deleting Section 16.16.240 and substituting the following:
“16.16.240
Local amendments to Standard Gas Code.
The following amendments, deletions, or additions to the 2000 Edition of the
Standard Gas Code are adopted by reference, as fully as though copied into such
Gas Code, and thereby made a part of the Gas Code.
A. Section 201 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new section 201.5 and substituting the following:
201.5 Interchangeability with the Standard Codes. The International Building Code shall be construed to mean the Standard Building Code. The International Property Maintenance Code shall be construed to mean the Property Standards Code of the Metropolitan Government. The International Mechanical Code shall be construed to mean the Standard Mechanical Code. The International Fuel Gas Code shall be construed to mean the Standard Gas Code. The International Plumbing Code shall be construed to mean the Standard Plumbing Code. The International Private Sewage Disposal Code shall be construed to mean the Subsurface Sewage Disposal Systems Code The ICC Electrical Code shall be construed to mean the National Electrical Code.
B. Section 202 of the 2000 Edition of the Standard Gas Code is hereby amended by adding the following new definition as follows:
ADMINISTRATIVE
AUTHORITY -- shall mean the Director of the Metropolitan Department of Codes
Administration, his deputy or duly authorized representative.
GAS OFFICIAL -- shall mean the Director of the Metropolitan Department of Codes
Administration, his deputy or duly authorized representative.
C. Section 202 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting the definition of “Code Official” and substituting the following:
CODE OFFICIAL -- shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
D. Section 304.11.2 and Figure 304.11(4) of the 2000 Edition of the Standard Gas Code are hereby amended by deleting the section and figure in their entirety.
E. Section 402.5 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 402.5 and substituting the following:
402.5 Maximum design operating pressure. The maximum design operating pressure for piping systems located inside buildings shall not exceed 5 psig (34 kPa gauge) unless approved by the authority having jurisdiction and one or more of the following conditions are met:
1. The piping system
may be threaded. Piping system over 5 psig shall be welded.
2. The piping is located in a ventilated chase or otherwise enclosed for protection
against accidental gas accumulation.
3. The piping is located inside buildings or separate areas of buildings used
exclusively for:
3.1 Industrial processing or heating,
3.2 Research,
3.3 Warehousing, or
3.4 Boiler or mechanical equipment rooms.
4. The piping is a temporary installation for buildings under construction.
F. Section 404.1 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 404.1 and substituting the following:
404.1 Prohibited
locations. Piping shall not be run or installed in or through a circulating
air duct, clothes chute, chimney or gas vent, ventilating duct, dumbwaiter,
or elevator shaft. Where the gas official finds that it is impossible to avoid
installing gas piping through or in building duct system for heat, ventilating
or air conditioning system, the gas pipe may be installed in a casing of noncombustible
rigid gas-tight material. Such casing shall comply with Section 311.
404.1.2 Gas piping shall be prohibited in plenum spaces unless such spaces are
accessible. This provision shall not apply to gas piping in non plenum concealed
locations. Shut-off valves and unions for gas piping shall be prohibited in
all concealed locations and all spaces used as plenums.
G. Section 404.3 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 404.3 and substituting the following:
404.3 Piping in
concealed locations. Portions of a piping system installed in concealed locations
shall not have unions, tubing fittings, right and left couplings, bushings,
compression couplings and swing joints made by combinations of fittings.
EXCEPTIONS:
1. Tubing joined by brazing.
2. Fittings listed for use in concealed locations.
404.3.1. Tubing in Partitions. This provision shall not apply to tubing which
pierces walls, floors, or partitions. Tubing shall not be run horizontally inside
hollow walls or partitions unless protected along its full concealed length
against physical damage. Tubing may be run vertically inside hollow walls or
partitions without protection along its entire concealed length provided and
the tubing is not rigidly secured.
H. Section 404.8 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new section 404.8.3 as follows:
404.8.3. Cathodic
protection shall be required on metallic gas piping installed underground. The
following chart may be used to determine requirement for anodes as to size and
number required:
Coated Pipe
Anode Spacing In Feet
Anode Weight ¾" 1" 2" 3"
1# 809' 643' 352' 238'
5# 1079' 857' 470' 317'
17# 1798' 1428' 783' 528'
Exception: Coated and wrapped metallic gas piping run underground that does
not exceed thirty (30) feet in length shall not require additional cathodic
protection.
I. Section 404.9 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 404.9 and substituting the following:
404.9. Minimum
burial depth and clearances. Underground piping systems shall be installed a
minimum depth of 18 inches (458 mm) below grade, except as provided for in 404.9.1
and 404.9.3
404.9.1 Individual outside appliances. Individual lines to outside lights, grills
or other appliances shall be installed a minimum of 8 inches (203 mm) below
finished grade, provided that such installation is approved and is installed
in locations not susceptible to physical damage.
404.9.2. Clearances. No gas piping shall be placed underground closer than eight
(8) inches from a water pipe, sewer line, or any other utility service line.
Underground gas piping shall be installed with enough clearance from any other
underground structure to avoid contact therewith, to allow proper maintenance,
and to protect against damage that might result from proximity to other structures.
In addition, underground plastic piping shall be installed with sufficient clearance,
or shall be insulated, from a source of heat so as to prevent the heat from
impairing the serviceability of the pipe.
404.9.3. Protection Against Damage.
Where soil conditions are unstable and settling of piping or foundation walls
or heavy vehicular traffic may occur, adequate measures shall be provided to
prevent excessive stressing of the piping. Piping shall be buried a sufficient
depth or covered in a manner so as to protect the piping from physical damage.
404.9.4. Cover Requirements. Underground piping systems shall be installed with
at least eighteen (18) inches of cover. The cover may be reduced to twelve (12)
inches if external damage to the pipe is not likely to result. If minimum of
twelve (12) inches of cover cannot be maintained, the pipe shall be installed
in conduit or bridged (shielded).
404.9.5. Separate Ditch for Gas Piping. The laying or installing of gas piping
in the same ditch with water, sewer, drainage pipe or any other utility service
line is prohibited except when approved by the administrative authority.
J. Section 404.10 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 404.10 and substituting the following:
404.10 Trenches. The trench shall be graded so that the pipe has a firm, substantially continuous bearing on the bottom of the trench. Where flooding of the trench is done to consolidate the backfill, care shall be exercised to see that the pipe is not floated from its firm bearing on the trench bottom.
K. Section 404.14.1 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new Section 404.14.1 Exception 3 as follows:
3. Plastic piping shall not be used for consumer's gas piping when operating pressures are in excess of 2 psi, unless approved by the Director of Codes Administration or his duly authorized representative.
L. Section 406.2 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 406.2 and substituting the following:
406.2 Test medium. The test medium shall be air, nitrogen, or carbon dioxide or an inert gas. Oxygen shall not be used. Fuel gas may be used in piping systems operating at pressures of one half (½) pound per square inch or less.
M. Sections 406.4.1 and 406.4.2 of the 2000 Edition of the Standard Gas Code are hereby amended by deleting Sections 406.4.1 and 406.4.2 and substituting the following:
406.4.1. Method of Testing. Low pressure (not in excess of 0.5 psi) gas piping shall withstand a pressure of at least 10.0 psi for a period of not less than twenty (20) minutes without showing any drop in pressure. For 2 psi or higher pressure piping must stand a pressure of at least 20 psi, but never less than ten (10) times the maximum pressure to which the piping will be subjected in operation, for a period of not less than twenty (20) minutes without showing any drop in pressure. An overnight test of larger piping systems may be required. The test shall be verified in writing on forms authorized by the Department of Codes Administration witnessed and signed. Retest or additional certification, in special situations, may be required by the Director of Codes Administration or by his/her duly authorized representative. Necessary apparatus for conducting the test shall be furnished by the permit holder.
N. Section 410.1 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 410.1 and substituting the following:
410.1 Pressure
regulators. A line pressure regulator shall be installed where the appliance
is designed to operate at a lower pressure than the supply pressure. Access
shall be provided to pressure regulators. Pressure regulators shall be protected
from physical damage. Regulators installed on the exterior of the building shall
be approved for outdoor installation.
410.1.1. Shutoff value. An accessible gas shutoff valve shall be provided upstream
of each gas pressure regulator. Where two gas pressure regulators are installed
in series in a single gas line, a manual valve is not required at the second
regulator.
410.1.2 Venting of Pressure Regulators. A vent line(s) from a gas appliance
pressure regulator and a bleed line(s) from a diaphragm type valve shall not
be connected to a common manifold terminating in a combustion chamber. Vent
lines shall not terminate in positive pressure type combustion chambers.
O. Chapter 4 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new Section 416 as follows:
Section 416
2# PSI Piping System.
416.1 General. 2 psi gas piping systems designed in accordance with this section
and other requirements of this code are intended for use where the building
service regulator has been set to deliver gas at 2 psi. Piping systems shall
be designed to allow a maximum pressure drop of one and one half (1½)
psi between the meter and the regulator that reduces the pressure to seven (7)
inch w.c. Piping systems shall be further designed to allow up to one (1) inch
w.c. pressure drop between the above first cut regulator and the appliance or
the appliance regulator if used.
416.2 Gas Piping
Materials. All piping shall be metallic material only, and comply with 403.
Piping installed for 2 psi pressure shall be (1) type L copper tubing, (2) refrigeration
service tubing having a wall thickness of not less than .030", (3) corrugated
stainless steel conduit, (4) iron pipe. All piping and tubing shall be sized
so as to not exceed the capacities shown on tables 1003A, 1003B, or 1003C. Iron
pipe already in service may be retained. Aluminum tubing will not be installed
or used for this service. All horizontal tubing shall be supported at approximately
four (4) foot intervals.
416.3 Marking. All piping in the 2 psi portion of the system shall be marked
at the beginning, all ends with a metal tag stating "2 psi." All such
tubing or piping must also be marked at intervals not to exceed six (6) feet
with approved means of identification designating 2 psi gas pressure.
416.4 Piping in Partitions. When copper tubing is installed in a hollow partition
in a new piping installation, a metallic sleeve, or equivalent means, shall
be used to protect the tubing where it passes through a wood plate or other
structural member of the wall. The sleeve, if used, shall extend at least four
(4) inches on either side of the structural member in the partition. Iron pipe
may be used for the sleeve. The ends must be reamed to avoid sharp edges which
may come in contact with copper tubing. Tubing in the partition shall have some
slack. Concealed tubing joints are prohibited.
416.5 General Piping. All fuel lines from the meter shall pass through the foundation
with iron pipe, then a pipe to flare adapter may be installed for the copper
tubing. In such case that the piping system cannot pass through the foundation,
iron pipe will run from the meter to the outside wall of structure and attach
with suitable pipe straps then adapt to copper tubing. Installation procedures
must guard against dirt, tubing cutting chips, or other material entering the
fuel line. Blow out lines before connecting and testing.
416.6 Joints and Fittings, Tubing. All joints and fittings in 2 psi tubing shall
be made with standard SAE heavy duty short shoulder flare fittings having a
forty-five (45) degree flare. All joints and fittings in 2 psi corrugated stainless
steel conduit shall be made with approved fitting design for that system. Brazed
or silver soldered joints made with an alloy having a melting temperature in
excess of 1000 degrees fahrenheit are permitted. Soft solder joints are not
permitted.
All joints in existing copper tubing must be inspected and tested before being
used for 2 psi service. All soft solder joints will be replaced with a flare
fitting or with a silver solder joint. All bends should be smooth without any
binds in tubing. Bending springs or tubing benders should be used.
416.7 MP Regulators.
MP pressure regulators installed in the 2 psi portions of the piping shall comply
with the following provisions:
416.7.1 The MP regulator shall comply with Sections 402.1 and 402.13 and shall
be stated by its manufacturer as being suitable for the inlet and outlet gas
pressures for which it is to be used.
416.7.2. The MP regulator shall maintain a reduced outlet pressure under lock-up
(no flow) conditions and shall be so installed on the piping system that they
cannot be concealed by building construction.
416.7.3. The capacity of the MP regulator, determined by published ratings of
its manufacturer, shall be adequate to supply the appliances served by it.
416.7.4. The MP pressure regulator shall be accessible for servicing and may
be located either indoors or outdoors. When located indoors, the regulator shall
be vented to outdoors or equipped with a vent limiting device, in either case
complying with Section 410.3.
416.7.5. The service regulator shall be set to deliver 2 psi, with flow of 30
CFH, after which the adjusting cap shall be sealed with a copper wire and lead
seal. The regulator will be marked with a red cap and a metal tag stating 2
psi attached. The gas meter will be installed with a Red index indicating 2
psi system.
416.8 The regulator
which reduces the pressure from 2 psi to seven (7) inch w.c. shall be located
as close as practical to the appliance which it serves. This regulator must
be installed where it cannot be concealed by building construction. The 2 psi
to seven (7) inch w.c. regulator must be vented to the outside atmosphere or
must be equipped with a vent limiter device. When installed for one appliance
only, the preferred location of the regulator and its shut off cock is above
the floor level and immediately adjacent to the appliance it serves.
416.9 Appliance regulators, when used, may be installed on or adjacent to the
appliance manifold. Appliance regulators are not required on manually operated
room heaters, ranges or similar appliances not equipped with a pilot. A pipe
nipple at least six (6) inches long, or equivalent tubing, must be installed
between the 2 psi to seven (7) inch w.c. regulator and the appliance regulator.
Existing appliance regulator shall be retained on any appliance, unless defective.
416.10 Manual Shutoff Valve. Where there is more than one MP regulator in the
complete piping system served by one meter, a listed shutoff valve shall be
installed immediately ahead of each MP regulator. A listed shutoff valve shall
be installed ahead of each 2 psi to seven (7) inch w.c. regulator. Individual
runs of tubing may be made to each appliance from a manifold. The cocks may
be at the manifold, but they must be easily accessible, and identified as to
the appliance served.
P. Section 502 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new Section 502.7 as follows:
502.7 Marking.
502.7.1 In those localities where solid and liquid fuels are used extensively,
gas vents shall be plainly and permanently identified by a label attached to
the wall or ceiling at a point where the vent connector enters the gas vent.
502.7.2 The label shall read: This gas vent is for appliances which burn gas.
Do not connect to solid or liquid fuel-burning appliances or incinerators.
502.7.3 The authority having jurisdiction shall determine whether its area constitutes
such a locality.
Q. Section 503.1 of the 2000 Edition of the Standard Gas Code is hereby amended by adding a new Section 503.1.1 as follows:
503.1.1 Equipment
Not Required to be Vented.
a. Listed ranges.
b. Built-in domestic cooking units listed and marked for optional venting.
c. Listed hot plates and listed laundry stoves.
d. Listed Infrared Radiant heaters (see Section 516.1.1).
e. A single listed booster type (automatic instantaneous) water heater, when
designed and used solely for the sanitizing rinse requirements of a National
Sanitation Foundation Class 1, 2, or 3 dishwashing machine, provided that the
input is limited to 50,000 Btu per hour, the storage capacity is limited to
12.5 gallons, and the heater is installed, with the draft hood in place and
unaltered, in a commercial kitchen having a mechanical exhaust system. When
installed in this manner, the draft hood outlet shall not be less than thirty-six
(36) inches vertically and six (6) inches horizontally from any surface other
than the heater.
f. Listed refrigerators.
g. Counter appliances.
h. Room heaters listed for unvented use shall not be installed in bathrooms
or bedrooms and in institutions such as homes for the aged, sanitariums, convalescent
homes, orphanages, etc.
i. Direct gas-fired make-up air heaters.
j. Other equipment listed for unvented use and not provided with flue collars.
k. Specialized equipment of limited input such as laboratory burners or gas
lights.
503.1.2. When any or all of this equipment is installed so the aggregate input rating exceeds 20 Btu per hour per cubic foot of room or space in which it is installed, one or more shall be provided with venting systems or other approved means for removing the vent gases to the outside atmosphere so the aggregate input rating of the remaining unvented equipment does not exceed the 20 Btu per hour per cubic foot figure. When the room or space in which the equipment is installed is directly connected to another room or space by a doorway, archway, or other opening of comparable size which cannot be closed, the volume of such adjacent room or space may be included in the calculations.
R. Section 602 of the 2000 Edition of the Standard Gas Code is hereby amended by adding the following new Section 602.4:
602.4 Installations
requirements. A decorative appliance for installation in a vented fireplace
shall be installed only in a vented fireplace having a working chimney flue
and constructed of noncombustible materials. These appliances shall not be thermostatically
controlled.
1. A listed decorative appliance for installation in a vented fireplace shall
be installed in accordance with its listing and the manufacturer's instructions.
2. An unlisted decorative appliance for installation in a vented fireplace shall
be installed in a fireplace having a permanent free opening, based on appliance
input rating and chimney height, equal to or greater than that specified in
Table 632.1.
S. Section 623.1.1 of the 2000 Edition of the Standard Gas Code is hereby amended by deleting Section 623.1.1 and substituting the following:
623.1.1 Installation
requirement. Water heaters other than the direct vent type shall be located
as close as practicable to the chimney or gas vent. They should be so located
as to provide short runs of water piping to the water heaters.
623.1.2 All gas water heaters installed in attics, on combustible floors or
in remote locations shall rest in pans of minimum 0.0276-inch (24 ga.) galvanized
sheet steel or equivalent with minimum depth of two (2) inches and shall have
a minimum clearance from the water heater of two (2) inches on all sides: the
pan shall be a sufficient size to receive all drippings or condensation from
such water heaters. All drain pans shall have a minimum one (1) inch drain.
No plastic pans will be permitted (See Section 504.7 of the Standard Plumbing
Code for other safety pan requirements).
Exception: Water heaters shall not be located in unheated and un-insulated spaces
except in unheated basements and garages.
623.1.3. Single-faucet automatic instantaneous water heaters. In addition to
the above, shall not be installed in kitchen sections of light housekeeping
rooms or rooms used by transients.
T. The 2000 Edition of the Standard Gas Code is hereby amended by adding the following new Appendix E:
Appendix E Suggested Method for Checking for Leakage.
E1. Use of Lights.
Artificial illumination used in connection with a search for gas leakage shall
be restricted to battery-operated flashlights (preferably of the safety type)
or approved safety lamps. In searching for leaks, electric switches should not
be operated. If electric lights are already turned on, they should not be turned
off.
E1.1 Checking for Leakage Using the Gas Meter. Immediately prior to the test
it should be determined that the meter is in operating condition and has not
been bypassed.
Checking for leakage can be done by carefully watching the test dial of the
meter to determine whether gas is passing through the meter. To assist in observing
any movement of the test hand, wet a small piece of paper and paste its edge
directly over the center line of the hand as soon as the gas is turned on. This
observation should be made with the test hand on the upstroke. The following
table can be used for determining length of observation time.
TABLE ETest Observation
Times forVarious Meter Dials
Dial StylesCubic Feet Test TimerMinutes
¼ 5
½ 5
1 7
2 10
5 20
10 30
In case careful observation of the test hand for a sufficient length of time reveals no movement, the piping shall be purged and a small gas burner turned on and lighted and the hand of the test dial again observed. If the dial hand moves (as it should), it will show that the meter is operating properly. If the test hand does not move or register flow of gas through the meter to the small burner, the meter is defective and the gas should be shut off and the serving gas supplier notified.”
Section 21. Section 16.16.260 of the Metropolitan Code of Laws hereby amended by deleting Section 16.16.260 and substituting the following:
MECHANICAL CODE SECTION
“16.16.260
Standard Mechanical Code--Local amendments.
The following amendments, deletions, or additions to the 2000 Edition of the
Standard Mechanical Code are adopted by reference, as fully as though copied
into such Mechanical Code, and thereby made a part of the Mechanical Code.
A. Section 201 of the 2000 Edition of the Standard Mechanical Code is amended by adding a new section 201.5 and substituting the following:
201.5 Interchangeability with the Standard Codes. The International Building Code shall be construed to mean the Standard Building Code. The International Property Maintenance Code shall be construed to mean the Property Standards Code of the Metropolitan Government. The International Mechanical Code shall be construed to mean the Standard Mechanical Code. The International Fuel Gas Code shall be construed to mean the Standard Gas Code. The International Plumbing Code shall be construed to mean the Standard Plumbing Code. The International Private Sewage Disposal Code shall be construed to mean the Subsurface Sewage Disposal Systems Code The ICC Electrical Code shall be construed to mean the National Electrical Code.
B. Section 202 of the 2000 Edition of the Standard Mechanical Code is hereby amended by adding the following new definition of as follows:
ADMINISTRATIVE AUTHORITY -- shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
C. Section 202 of the 2000 Edition of the Standard Mechanical Code is hereby amended by deleting the definition of “Code Official” and substituting the following:
CODE OFFICIAL -- shall mean the Director of the Metropolitan Department of Codes Administration, his deputy or duly authorized representative.
D. Table 403.3 of the 2000 Edition of the Standard Mechanical Code is hereby amended by deleting Table 403.3 and substituting the following:
TABLE 403.3
REQUIRED OUTDOOR VENTILATION AIR
OCCUPANCYCLASSIFICATION ESTIMATED MAXIMUMOCCUPANT LOADPERSONS PER 1,000SQUARE
FEET{a} OUTDOOR AIR[cubic feet per minute (cfm)per person] UNLESS NOTED{e}
Correctional facilitiesCellsDining hallsGuard stations 2010040 201515
Dry cleaners, laundriesCoin-operate dry cleaner Coin-operated laundries Commercial
dry cleaner Commercial laundry Storage, pick up 2020301030 1515302535
EducationAuditoriums Classroom Corridors LaboratoriesLibraries Locker roomsMusic
rooms Smoking lounges{b,g} Training shops Bathrooms 15050--3020--507030 15150.10
cfm/ft220150.50 cfm/ft21560201.0 cfm/ft2
Food & beverage service Bars, cocktail lounges Cafeteria, fast food Dining
rooms Kitchens (cooking){f,g} …Bathrooms 1001007020 302020151.5 cfm/ft2
Hospitals, nursing and Convalescent homes Autopsy rooms{b} Medical procedure
rooms Operating rooms Patient rooms Physical therapy Recovery and ICU --2020102020
0.50 cfm /ft21530251515
Hotels, motels, resorts And dormitories Assembly rooms Bathrooms{b,g} Bedrooms
Conference rooms Dorm sleeping areas Gambling casinos Living rooms Lobbies 120----5020120--30
151.5 cfm /ft230 cfm per room20153030 cfm per room15
Offices Conference rooms Office spaces Reception areas Telecommunication centers
and data entry 5076060 20201520
Private dwellings multiple Living areas{c}Kitchens{g}Toilet rooms andBathrooms{g}Garages,
separate for each dwellingGarages, common for multiple units{b} Based uponNumber
of bedroomsFirst bedroom: 2; each additional bedroom: 1 0.35 air changes per
hour{a} or 15 cfm per person, whichever is greater100 cfm intermittent or 25
cfm continuous1.0 cfm /ft2100 cfm per car1.5 cfm/ft2
Public spaces Corridors and utilities Elevators{g} Locker & dress rooms
{b} Toilet rooms{b,g} Smoking lounges{b,g} --------70 0.05 cfm/ft21.00 cfm/ft20.5
cfm/ft275 cfm per water closet or urinal60
Retail stores, sales floors And showroom floors Basement and street Dressing
rooms Malls and arcades Shipping & receiving Smoking lounges{b} Storage
rooms Upper floors Warehouses Bathrooms --------70-------- 0.30 cfm/ft20.20
cfm/ft20.20 cfm/ft20.15 cfm/ft2600.15 cfm/ft20.20 cfm/ft20.05 cfm/ft21.0 cfm/ft2
Specialty shops Auto service stations Barber Beauty Clothiers, furniture Florists
Hardware, drugs, fabrics Pet shops Reducing salons Supermarkets --2525--88--208
1.5 cfm/ft215250.30 cfm/ft215151.00 cfm/ft21515
Theaters Auditoriums Lobbies Stages, studios Ticket booths 1501507060 15201520
Transportation Platforms Vehicles Waiting rooms 100150100 151515
Workrooms Bank vaults Darkrooms Duplicating, printing Meat processing{c} Pharmacy
Photo studios 5----102010 150.50 cfm/ft20.50 cfm/ft2151515
Sports and amusement Ballrooms and discos Bowling alleys (seating areas) Game
rooms Ice arenas Playing floors (gyms) Spectator areas Swimming pools (pool
and deck area) 1007070--30150-- 252525 0.50 cfm/ft220150.50 cfm/ft2
Storage Repair garages, enclosed parking garages{d} Warehouses ---- 1.5 cfm/ft20.50
cfm/ft2
For SI: 1 cubic
foot per minute = 0.0004719 ms3/s,
1 ton = 908 kg,
1 cubic foot per minute per square foot = 0.00508 m3/(s • m^2),
ºC = [(ºF) -32]/1.8, 1 square foot = 0.0929 m2.
{a} Based upon
net floor area.
{b} Mechanical exhaust required and the recirculation of air from such space
as permitted by Section 403.2.1 is prohibited (see Section 403.2.1).
{c} Spaces unheated or maintained below 50ºF are not covered by these requirements
unless the occupancy is continuous.
{d} Ventilation systems in enclosed parking garages shall comply with Section
404. A mechanical ventilation system shall not be required in garages having
a floor area not exceeding 850 square feet and used for the storage of not more
than four vehicles or trucks of 1 ton maximum capacity.
{e} Where the ventilation rate is expressed in cfm/ft2, such rate is based upon
cubic feet per minute per square foot of the floor area being ventilated.
{f} The sum of the outdoor and transfer air from adjacent spaces shall be sufficient
to provide an exhaust rate of not less than 1.5 cfm/ft2.
{g} Transfer air permitted in accordance with Section 403.2.2.
E. Sections 506, 507, 508 and 509 of the 2000 Standard Mechanical Code are hereby amended by deleting Sections 506, 507, 508 and 509 and substituting the following:
Grease hood duct systems must comply with NFPA 96 2000 Edition.
F. Section 601 of the 2000 Standard Mechanical Code is hereby amended by adding a new Section 601.4. as follows:
601.4 Insulation required. All ductwork installed in non-conditioned and not completely conditioned areas such as crawl, attic and the floor/ceiling assembly shall be insulated
G. Section 607.5.2 Exception 1 of the 2000 Standard Mechanical Code is hereby amended by deleting Section 607.5.2 Exception 1 and substituting the following:
Steel exhaust air subducts extend not less than 22 inches (559 mm) vertically in an exhaust riser duct installed in a shaft providing there is a continuous airflow upward to the outdoors.”
Section 22. Section16.20.150N(1.) of the Metropolitan Code of Laws is hereby amended by deleting Section 16.20.150N(1.) and substituting the following:
“(1) Any commercial building, industrial building or other structures and multifamily dwelling unit buildings exceeding three floors.”
Section 23. Section16.28.150 of the Metropolitan Code of Laws is hereby amended by deleting Section 16.28.150 and substituting the following:
“16.28.150 Foundations permit / Utility installations.
A. When application for a permit to erect or enlarge a building has been filed and pending issuance of such permit, the director of codes administration may, at his discretion, issue a special permit for the foundations of such building. The holder of such a special permit shall proceed at his own risk and without assurance that a permit for the superstructure will be granted.
B. When utilities
are to be installed within an individual parcel of land to connect to a building
or structure, a utility permit may be issued.
Exceptions: Utilities installed by the Utility Company
C. The partial permit fee for the foundation/utility installation shall be not less than five percent (5.0%) of the total building as per Section 16.28.120.”
Section 24. Chapter 16.28. of the Metropolitan Code of Laws is hereby amended by adding a new Section 16.28.152 as follows:
“16.28.152 Structural Framing permit
A. When application for a permit to erect or enlarge a building has been filed and pending issuance of such permit, the director of codes administration may, at his discretion, issue a special permit for the structural framing of such building. This permit would include installing columns, floor systems. bearing walls, but not roof systems or non bearing exterior walls.
B. The electrical, plumbing, and HVAC systems may be “rough-in” in the non-tenant areas.
C. The partial permit for the structural framing fee shall be not less than fifty percent (50.0%) of the total building valuation as per Section 16.28.120.”
Section 25. Chapter 16.28. of the Metropolitan Code of Laws is hereby amended by adding a new Section 16.28.154 as follows:
“16.28.154 Building Shell permit.
A. When application for a permit to erect or enlarge a building has been filed and pending issuance of such permit, the director of codes administration may, at his discretion, issue a special permit for the shell of such building.
B. This permit would include installing exterior walls and the roof system. The electrical, plumbing, and HVAC systems may be “rough-in” in the non-tenant areas.
C. The partial permit for the shell fee shall be not less than sixty- five percent (65.0%) of the total building valuation as per Section 16.28.120. If a structural framing permit has been previously issued, the partial permit for the shell fee shall be not less than fifteen percent (15.0%) of the total building valuation as per Section 16.28.120.’’
Section 26. Chapter 16.28. of the Metropolitan Code of Laws is hereby amended by adding a new Section 16.28.156 as follows:
16.28.154 Building Shell Finish-out permit.
A. When application for a permit to erect or enlarge a building has been filed and pending issuance of such permit, the director of codes administration may, at his discretion, issue a special permit for finishing- out the interior of the shell of such building. This permit would include installing all interior finishes of each tenant space.
B. The electrical, plumbing, and HVAC permits may be issued to complete finish out of the installation of each system.
C. The partial permit for the tenant finish-out fee shall be not less than forty-five percent (45.0%) of the total building valuation as per Section 16.28.120 for a building that the total tenant area is substantiality less that the gross area of the building. If the tenant is basically equal to the gross area of the building, the partial permit for the tenant finish-out permit fee shall be not less than thirty percent (30.0%) of the total building valuation as per Section 16.28.120.
Section 27. Section16.28.170B of the Metropolitan Code of Laws is hereby amended by deleting Section 16.28.170B and substituting the following:
“B. It shall be the duty of the director of public works to see that the street lines are not encroached upon in any manner whatsoever, except as provided in Section 3202, of the Standard Building Code and other applicable sections of the Standard Building Code.”
Section 28. Section 16.48.010 of the Metropolitan Code of Laws is hereby amended by deleting Section 16.48.010 and substituting the following:
“16.48.010
Variances authorized when--Guidelines.
A. To promote conservation and rehabilitation of existing buildings, alterations,
repairs, or change of use and occupancy may be made where such rehabilitation
conforms to the intent of this code as established by the Director. The Director
may exercise discretionary authority, subject to appeal, to vary or modify in
whole or in part the application of any provision of this code where compliance
with such provision would create practical difficulty or undue hardship, and
further subject to Sections 3405, D102.1, and D102.2 of the Standard Building
Code.
B. Such variances or modifications shall be consistent with the intent of this code, which is to achieve acceptable levels of safety for the general public. The Director may require documented justification for any request for such variances or modifications from any code provision to be prepared in written form, supported by technical or other data deemed necessary and that proposal shall become a part of the permanent records of the Department of Codes Administration.
C. The Director
may adopt a committee to develop such rules, regulations and guidelines such
as, but not limited to, “Chapter 34, Section 3409 Compliance Alternatives,
of the Standard Building Code” as may be necessary to carry out the intent
of this chapter, which is to allow discretion and flexibility in the rehabilitation
of existing buildings.
D. The director shall create a rehab committee that shall meet on as needed
basis. The members of committee shall be the Assistant Director of the codes
department, the Chief Plans Examiner or the Chief Building Inspector and the
Assistant Fire Marshal or his designated deputy. The decision of the Rehab committee
may be subject to Chapter 2.80 (the board of fire and building appeals).”
Section 29. Sections 2.20.040 of the Metropolitan Code of Laws is hereby amended by adding the following new sub-sections C and D to Section 2.20.040:
C. Emergencies
– Powers of director. The decision of the director of codes administration
shall be finial in cases of emergency, without notice to the owner, which in
his opinion involved imminent danger to human life or health. The director shall
immediately cause such building, structure or portion thereof to be made safe
or removed. For this purpose, the director may enter at once such building or
structure or the premises upon which the same is located, or abutting land or
structures, with such assistances and at such cost as he may deem necessary.
He may vacate adjacent structures and protect the public by appropriate barricades
or such other means as may be necessary, and for this purpose may close a public
or private street, alley or means of egress.
D. Emergencies – Notification of director – Responsibilities. In
any case of emergency, the director of codes administration or his deputy shall
be notified by the fire department, the police department or any other metropolitan
department as may be deemed necessary, and he shall immediately proceed to the
scene of any disaster caused by a calamity, flood, fire or any act of God and
render assistance and post such notice as may be necessary to warn the general
public of imminent or latent danger of collapse of any building, structure or
appurtenance thereto cause by reason of such calamity, fire flood or act of
God. The director may request and shall receive, so far as may be necessary
in the discharge of this duties, the assistance and cooperation of other metropolitan
officials.
Section 30. Sections 16.52.080 and 16.52.090 of the Metropolitan Code of Laws is hereby amended by deleting Sections 16.52.080 and 16.52.090 in their entirety.
Section 31. That
these Sections of this Ordinance shall take effect immediately upon signage,
the welfare of the Metropolitan Government of Nashville and Davidson County
requiring it.